- ページ 4
コントローラー DROPSA ADVANCED LUBRICATION CONTROLLERのPDF 取扱説明書および製品データシートをオンラインで閲覧またはダウンロードできます。DROPSA ADVANCED LUBRICATION CONTROLLER 4 ページ。 With quick remote configuration
Fig. 4. Remote Transmitt Module.
5. ORDERING INFORMATION:
Part No.
Description
1639076
VIP Controller 24V Box Version.
1639077
VIP Controller 110/230V Box Version.
VIP Controller 24V Panel Mounted
1639080
Version.
VIP Controller 110/230V Panel Mounted
1639084
Version.
1639088
Remote Transmit Module.
VIP Controller 220V Single Phase in
1639081
Steel Enclosure.
VIP Controller 380V Three Phase in
1639087
Steel Enclosure.
6. SPARES
No user serviceable parts inside.
7. SAFETY REQUIREMENTS
These Controllers must be installed and operated in ac-
cordance with the requirements of this Instruction Sheet
and should not be used for any purpose than that specified
without the agreement of the suppliers.
In addition to the need to observe general safety require-
ments the following specific hazards apply:
Before installing or removing Advanced Lubrication Con-
ALEX/DROPSA
DROPSA UK LTD.
Vimodrone (MI)
Egham, SURREY.
Tel: (02) 250791
Tel: (01784) 431177
Fax: (02) 25079767
Fax: (01784) 438598
© Copyright Dropsa - all rights reserved. Reproduction of any part of this document is strictly forbidden without prior consent from Dropsa.
Dropsa reserve the right to withdraw or modify specifications without prior notice.
4
trollers from the system disconnect and isolate all power
supplies.
8. OPERATING ENVIRONMENT
Controllers must not be operated in excessively corrosive
or aggressive environments. If in doubt, please contact
our Technical Office.
9. DIAGNOSTIC TABLE:
ALARM
CODES
AO1
AO2
AO3
AO4
AO5
DROPSA GMBH
DROPSA FRANCE - AME.
Düsseldorf, GERMANY.
Garges-Les-Gonesse, CEDEX.
Tel: (0211) 394011
Tel: (01) 399.300.33
Fax: (0211) 394013
Fax: (01) 398.626.36
'VIP' ADVANCED LUBRICATION CONTROLLER
DESCRIPTION
OF FAULT
No parameters set.
Set parameters.
Low Level alarm.
Add lubricant to the
system
The change-over
Check for loose
contact (in SEP
fittings
mode) has not
blockages
cycled within the
progressive system
specified 'Pump
and rectify.
ON ' times.
PS Mode: Pressure
Check pressure
was already high
switch and replace
before the start of
if necessary.
the cycle.
PS Mode: The
Check for leakage
system did not
from loose fitting
achieve pressure
and rectify.
during the specified
cycle times.
DROPSA CORPORATION
Houston, TEXAS.
Tel: (713) 462-1061
Fax: (713) 462-4027
ACTION
and
in