E. Standard Communication Panel: The UPS will include a standard easy to use commu-
nication panel. The UPS communication panel will include pushbuttons that will permit the
user to safely command the UPS.

2.5 SYSTEM CONTROLS AND INDICATORS

A. Front Panel LCD Display: The UPS control panel shall provide a LCD display. The indi-
cation of UPS status, metering, battery status, alarm event log and advanced operational
features will be available. The display provides access to:
1. Measurements, status indications and events
2. Menu protected by a password, used to make specific settings
3. Event log with time stamping
4. Access to all measurements
B. System Parameters Monitored (data displayed): The visual display will display the fol-
lowing system parameters based on true RMS metering:
1. Measurements
a. Input voltage indicator
b. UPS output voltage indicator
c. UPS output current indicators
d. DC voltage indicators
2. Status indications and events
e. Load on battery
f. Load on UPS
g. Load on automatic bypass
h. Low-battery warning
i. General alarm
j. Additional indications shall provide maintenance assistance