コントローラー Auber Instruments SYL-2362BのPDF 取扱説明書をオンラインで閲覧またはダウンロードできます。Auber Instruments SYL-2362B 5 ページ。 Pid temperature controller

Auber Instruments SYL-2362B 取扱説明書
AUBER INSTRUMENTS
Instruction Manual
Caution
 This controller is intended to control equipment under normal operating
conditions. If failure or malfunction of it could lead to an abnormal operating
condition that could cause personal injury or damage to the equipment or
other property, other devices (limit or safety controls) or systems (alarm or
supervisory) intended to warn of or protect against failure or malfunction of
the controller must be incorporated into and maintained as part of the
control system.
 Installing the rubber gasket supplied will protect the controller front panel
from dust and water splash (IP54 rating). Additional protection is needed
for higher IP rating.
 This controller carries a 90-day warranty. This warranty is limited to the
controller only.
1. Features
 The PID control with artificial intelligent enhancement for precision
temperature control.
 Auto-tuning function can find the best PID parameter automatically.
 On/off control mode for refrigerator, motor and solenoid valve control
application.
 Bumpless transfer between Auto and Manual control.
 Limit control for safety protection and special applications.
 The output can be set for SSR output control or relay contactor control by
the user.
 Two contact relays can be configured as one PID and one alarm output,
dual alarm outputs, or dual On/off control.
 Support 10 different types of commonly used temperature sensor inputs.
2. Specification
Thermocouple (TC): K, E, S, R, J, T, B, WRe3/25
Input type
RTD(Resistance temperature detector): Pt100, Cu50
Input range
See table 2
Display
Dual lines, four digits, °F or °C
Display resolution
1°C, 1°F; or 0.1°C, 0.1°F with Pt100
Accuracy
±0.2% or ±1 unit of full input range
Control mode
PID, On-off. Limit, Manual
Output mode
Relay contact: 3A at 240VAC, SSR: 8VDC, 40 mA.
Alarm
Process high/low alarm
Power consumption
<2 Watt
Power supply
12-30V DC, 12-18V AC (with diode)
Sample rate
4 samples/sec
Operating condition
0 ~ 50 °C, ≤ 85% RH
Mounting cutout
45 x 45 mm
Dimension
48x48x75mm (1/16 DIN)
2018.07
SYL-2362B PID TEMPERATURE CONTROLLER
INSTRUCTION MANUAL
Version 2.6
3. Front Panel and Operation
Figure 1. Front panel
① AL-1 Relay J1 output indicator
AL-2 Relay J2 output indicator
AT/M- On for manual mode. Blinking during auto-tuning process
OUT- SSR output indicator
② Value increment/Select next parameter
③ Value decrement/Select previous parameter
④ Auto tuning/Digit shift
⑤ Set/Confirm/Manual Auto switching/Reset (for Limit control mode)
⑥ Measured temperature, or, Process Value (PV)
⑦ Set temperature, or, Set Value (SV)
4. Terminal Wiring (back view)
SSR
-
+
6
11
12
1
2
-
+
Power
Input
Figure 2. Wiring diagram
4.1 Sensor connection
4.1.1 Thermocouple
The thermocouple should be connected to terminals 9 and 10. Make sure that
polarity is correct. There are two commonly used color codes for the K type
thermocouple. US color code uses yellow (positive) and red (negative).
Imported DIN color code uses red (positive) and green/blue (negative). The
temperature reading will decrease as temperature increases if the connection
is reversed.
WWW.AUBERINS.COM
TC
RTD
+ -
W
R
R
8
9
10
7
NC
13
J2
NO
14
3
4
5
J1
NC
NO
P1/5