- ページ 3

コントローラー AuCom CSX-037のPDF ユーザーマニュアルをオンラインで閲覧またはダウンロードできます。AuCom CSX-037 13 ページ。
AuCom CSX-037 にも: ユーザーマニュアル (12 ページ)

Section 3
3.1

Power Terminations

3.2

Control Voltages

CSX soft starters can be supplied in either of two control voltage configurations:
CSX-xxx-xx-C1 ..... 110-240 VAC (+ 10% / - 15%) or 380-440 VAC (+ 10% / - 15%)
CSX-xxx-xx-C2 ..... 24 VAC/VDC (± 20%)
WARNING
Always apply control voltage before (or with) mains voltage.
CAUTION
With 24 VAC/VDC use contacts rated for low voltage and low current (gold flash or similar).
3.3

Control Circuits

Start/stop. To reset a trip, close then open 02.
Start.
Stop. To reset a trip, close then open 02.
WARNING
Isolate the soft starter completely from the power supply before attempting any work on the
starter or motor. Control terminals may be at phase voltage potential.
710-02407-00G

Electrical Installation

L1/1, L2/3, L3/5,T1/2, T2/4, T3/6
mm
(AWG)
2
007 ~ 030
037 ~ 055
10 - 35
25 - 50
(8 - 2)
(4 - 1/0)
10 - 35
25 - 50
14
(8 - 2)
(0.55)
(4 - 1/0)
mm (inch)
Torx (T20)
Torx (T20)
3 Nm
4 Nm
2.2 f t-lb
2.9 f t-lb
7 mm
7 mm
3 Nm
4 Nm
2.2 f t-lb
2.9 f t-lb
Two-wire
ELECTRICAL INSTALLATION
A1, A2, A3, 01, 02, B4,
075 ~ 1 10
0.14 - 1.5
11
N.A.
(26 - 16)
(0.43)
26
Ø 8.5
(1.02)
(0.33)
0.14 - 1.5
14
N.A.
(0.55)
(26 - 16)
mm (inch)
mm (inch)
N.A.
N.A.
N.A.
CSX
B5, 13, 14, 23, 24
mm
(AWG)
2
007 ~ 1 10
6
(0.24)
mm (inch)
3.5 mm
0.5 Nm max
4.4 in-lb max
Three-wire
Page 3