Configuration
4
Configuration
4.1
Anybus Configuration Manager
The data exchange between the interfaces in the Anybus X-gateway is configured using the
Windows-based configuration tool Anybus Configuration Manager, which can be downloaded
from www.anybus.com/support.
Fig. 5
Anybus Configuration Manager
Input I/O data Size (bytes)
Output I/O data Size (bytes)
Input Parameter data Size (bytes)
Output Parameter data Size (bytes)
Offline option
Control word/Status word
4.2
Network Configuration
Each device in a PROFIBUS network is associated with a GSD (General Station Description)
file. This file contains information about the device and is required by the PROFIBUS network
configuration tool when adding the device to the network.
The GSD file for the Anybus X-gateway PROFIBUS Slave Interface as well as a free Windows-
based PROFIBUS network configuration tool called Anybus NetTool are available for download
at www.anybus.com/support, where you will also find additional documentation.
®
Anybus
X-gateway
™
PROFIBUS Slave Interface Network Guide
The amount of input I/O data to exchange on the PROFIBUS
network.
The amount of output I/O data to exchange on the PROFIBUS
network
The amount of input Parameter data to exchange on the
PROFIBUS network.
The amount of output Parameter data to exchange on the
PROFIBUS network
The action to perform if the network goes offline. The gateway can
either freeze (keep the current value) or clear (set to zero) the
data from the offline network.
Enables/disables representation of the Control/Status word.
9 (12)