- ページ 6
セキュリティシステム Concoa 529 5106-01-120のPDF 据付・取扱説明書をオンラインで閲覧またはダウンロードできます。Concoa 529 5106-01-120 13 ページ。
OPTION 2 (continued)
Cut the 6 conductor cable to length. Remove the outer jacket of the cable to expose approximately 11⁄2
inches of the internal conductors. Strip away 1⁄4 inch of the insulation on each of the 6 conductors. Tin
the leads of the conductors. Slide the protective cover, cable retainer, and locking nut for the circular
connector over one end of the cable as shown in Figure 5.
SYSTEM
LEFT BANK
RIGHT BANK
Using the pin assignments shown in Table 2 and the connector view in Figure 6, solder the wires to the
appropriate pins. After soldering is complete attache the cable cover, cable retainer, and locking nut to
each of the circular connector plugs.
Plug the one side of the cable into the Remote Alarm and secure it by turning the locking nut until it
locks. Plug the other circular connector into the Autoswith securing it by turning the locking nut until
it locks.
Cable Retainer Tabs
Cable Retainer
Cable Cover
Table 2
AutoSwitch
Connector
Pin #
1
2
4
5
3
6
Figure 6
Locking Nut
Figure 5
Remote Alarm
Connector
Pin #
1
LBSW status
2
4
RBSW status
5
3
6
notch
-6-
Plug
Function
alarm
alarm
+12
Gnd