- ページ 6

ケーブルとコネクター DuctSox IHSのPDF インストレーション・マニュアルをオンラインで閲覧またはダウンロードできます。DuctSox IHS 12 ページ。 Hoops cable

Hoops (IHS) Cable
DuctSox
®
Installation Manual
Step 3
1.5 in (38 mm)
Determine placement of cable (both cable path and elevation). The cable
must be mounted 1.5 in (38 mm) above the 12:00 location of the DuctSox.
Intermediate Cable supports are spaced no more than 30 ft (9150 mm).
T's
There should be roughly 12 in (305 mm) from sidewall of DuctSox to the closest
edge of any knee-bracing. Structure too close to the main run may cause
premature failure due to abrasion from the structure.
NOTE: Offset distance of branch knee-brace from main trunk is approximately
half of the main trunk diameter plus 12 in (305 mm).
Elbows
Extended straps on heels of elbows are provided for support to cable suspension (Figure A). Vertical elbows are also
supported by extended straps (Figure B).
Figure A
Figure B
6
Publication: AMEN00415 2021-02-26