The AnyWireASLINK system enables selection of 2-wire type slave unit or 4-wire
type slave unit depending on load current.
When the load current is small, simpli ed wiring is enabled by using the 2-wire
type (non-isolated) slave unit, without necessity of local power supply.
In the case where load concentration is expected, or to give priority to the number
of units to connect, the 4-wire type (isolated) slave unit that supports local power
supply can be connected in combination with the 2-wire type.
For input or driving load with an external power supply, be sure to use the 4-wire
type (isolated) slave unit.
[System Configuration Example]
■Connection with 2-wire (non-isolated) terminals only
Red:
Red: DP
DP
AnyWireASLINK
master
Black:
Black: DN
DN
Red: DP
*
24V DC
Black: DN
*
Make sure to use a
24V DC stabilized
power supply for the
Red: DP
power supply to be
connected.
Black: DN
*
When complying with
the UL Standard, make
Red: DP
sure to use a 24V DC
stabilized power supply
of "NEC Class 2
Black: DN
Output."
Red: DP
Black: DN
General-purpose
cabtyre cable
Dedicated at cable
1.25mm
(2-wire)
2
2P link connector is
convenient for
branching.
The sum of the
portions of DP, DN is
the total line length.
Black: DN
Red: DP
AnyWireASLINK terminator
One terminator should be connected to the DP, DN
terminal farthest from the AnyWireASLINK master unit.
Connect it correctly so as not to set the wrong polarity.
■Relationship between the size and length of
the transmission line and the supply current (Table 1)
Supply current on the transmission line (DP, DN)
Size of
the transmission
Total length:
line (DP, DN)
50m or less
1.25mm
MAX 2A
2
0.75mm
2
MAX 1.2A
0.5mm
MAX 0.8A
2
- Refer to Table 1 so that the size and length of the transmission
CAUTION
line and the allowable supply current lie within an appropriate
range.
- Connect the same symbols (DP, DN) correctly between the AnyWireASLINK
master unit and each device.
- The branching length or branch number has no limitation.
- Include the length of the cable provided with the terminal in the "total line length."
- Connect the terminator (with polarity) on the transmission line terminal farthest
from the AnyWireASLINK master unit.
2 points
2 points
Photoelectric head
Fiber unit
Photoelectric head 0
Photoelectric head 1
Photoelectric head 2
2 points
Black: DN
The branching
2 points
has no limitation.
Red: DP
2 points
Red: DP
Total length: Over 50m,
Total length: Over 100m,
no longer than 100m
no longer than 200m
MAX 1A
MAX 0.5A
MAX 0.6A
MAX 0.3A
MAX 0.4A
MAX 0.2A
■Example of mixed installation with 2-wire (non-isolated) and
4-wire (isolated) terminals
AnyWireASLINK
master
General-purpose
power supply lter
*
24V DC
Dedicated at cable
1.25mm
(4-wire)
2
4P link connector is
convenient for
branching.
Black: DN
2 points
The sum of the
portions of DP, DN is
the total line length.
24V DC
CAUTION
always use a 4-wire (isolated) terminal.
Otherwise, malfunction may be caused.
-L*F1011 2/11-
Red:
Red: DP
DP
2 points
Black:
Black: DN
DN
ASLINK
lter
Red: DP
2 points
Black: DN
Red: DP
Black: DN
Red: DP
Black: DN
Red: DP
Black: DN
Green: 24V
White: 0V
Red: DP
Black: DN
Green: 24V
White: 0V
The branching
has no limitation.
Black: DN
Red: DP
*
AnyWireASLINK terminator
One terminator should be connected to the DP, DN
terminal farthest from the AnyWireASLINK master unit.
Connect it correctly so as not to set the wrong polarity.
To connect loads (e.g. I/O ports) that are
controlled with a power supply other than the
one used for the AnyWireASLINK system,
8 points
Red: DP
Black: DN
Photoelectric head
Photoelectric head 0
Photoelectric head 1
Photoelectric head 2
Photoelectric head 3
Fiber unit
Fiber unit
Fiber unit
Fiber unit
8 points
Black: DN
2 points
Red: DP
2 points
Red: DP
Black: DN
2 points