■Automatic address/parameter setting (for master unit only)
This parameter speci es whether the automatic address/parameter
setting is enabled or not.
- Address Writer (ARW-04): Parameter 17
Variable
Description
0
Automatic setting is disabled.
Only automatic address setting is enabled.
1
2
Only automatic parameter setting is enabled.
*
Linked with the parameters of the master unit.
3
Automatic address and parameter settings are enabled.
This function enables address and parameter settings of the master
unit to be automatically re ected on slave units. When the automatic
setting mode is enabled (value 1, 2 or 3), an address and/or
parameter registered in the master unit will be automatically assigned
to each slave unit.
Example)
Assignment
If the
parameter 17
is set to "1"
Address setting "0"
■7-segment display orientation change setting (for master unit only)
This function is used to turn the 7-segment display orientation by 180˚.
This function is useful when indication is dif cult to see due to
orientation of the unit.
- Address Writer (ARW-04): Parameter 18
Variable
Description
0
Normal indication
1
180˚ inverted indication
0: Normal indication
Fiber side
1: 180˚ inverted indication
[Monitor Display]
LED
Display status
name
Lit
Transmission error, I/O power supply drop
LINK
The transmission signal and the 24V power are
Flashing
(Green)
both supplied.
Unlit
No power
I/O power supply drop, sensing level drop
Lit
ALM
Slave unit voltage drop (disconnection and
Flashing
(Red)
reverse connection of DP and DN lines included)
Unlit
Normal
Alternate ashing
LINK
When the master unit has detected that the unit
LINK
ALM
ID (address) is either duplicated or unregistered.
ALM
Lit
ON
IN
(Orange)
Unlit
OFF
LED indicators
7-segment display
Threshold
display
Light receiving level display
The display section is the same for master and slave units.
Factory
setting: 0
"3"
"2"
"1"
Factory setting: 0
Transmission side
Description
LINK
IN
ALM
LINK
IN
ALM
[Troubleshooting]
If the following errors are indicated on the display window of
ASLINKAMP, take the following actions.
LINK
IN
○
○
Unlit
Unlit
●
○
Lit
Unlit
◎
○
Flashing
Unlit
(alternates with
a 0.5 sec
interval)
Slave
-
-
Slave
Slave
Master
■Unit voltage (DP-DN) drop detection
Flashing
The display section is the same for master and slave units.
Check the following and eliminate the relevant cause.
- If the 24V DC power supply voltage to the AnyWireASLINK master unit is in
the allowable voltage range
- If there is any loose terminal or poor contact on the trunk and branch lines
- If the current on the unit and connected load current satisfy the system
conditions
■Abnormal voltage detection
If the voltage of 24V DC power supplied to the unit becomes signi cantly low
(near 16V), the message "dc24 Lo" is displayed and the unit stops functioning.
Check the supply voltage and take actions to increase the voltage to the
allowable range.
If the following error is indicated on the address writer, take the
following action.
Display
Cause
The parameter setting is
【E-0303】
incorrect.
Should any of the following apply, take the following actions.
Symptom
Remedy
Detection is
- Is the wiring correct?
disabled
- Is the power supplied to the AnyWireASLINK system?
- Are the addresses set?
- Is the unit used in the speci ed input range?
Setting cannot
- Is the wiring correct?
be made with
the address
writer
- Is the power supplied to the AnyWireASLINK system?
- Is the protective cover opened during the setting?
- Are the parameters set correctly?
-L*F1011 9/11-
ALM
Cause
- The AnyWireASLINK
- Check if there is a disconnection between
○
transmission signal is
Unlit
not connected.
- The AnyWireASLINK
- Check the power supply of
system is not turned
on.
- The transmission signal
- Reconnect the power to the
○
wave is not received
Unlit
because the DP-DN line
is connected directly to
the 24-0V line.
- The address of
- Assign an address other than 255.
◎
Flashing
ASLINKAMP remains
to be "255" (factory
(alternates with
setting).
a 0.5 sec
interval)
- The address of
- Look for a unit that has the same
ASLINKAMP is
duplicated.
- The internal voltage of
- Reduce the number of units
◎
ASLINKAMP is low.
Flashing
(Lit for 0.2 sec,
- Disconnection or
unlit for 1.0 sec)
reverse connection of
- Make the transmission line between
DP-DN line
LINK
IN
ALM
Remedy
Refer to the parameter correspondence
table and correct the setting.
Re-check the connections of the transmission line and the power
→
supply line.
Check the power supply.
→
Set the addresses.
→
Use it in the speci ed detection range.
→
Re-check the connection of the transmission line and see if the
→
transmission signal is sent.
Check the power supply.
→
Open the protective cover. Setting cannot be made with the
→
cover closed.
Refer to the parameter correspondence table and correct the
→
setting.
Remedy
the ASLINKAMP and the AnyWireASLINK
system and restore the connection.
AnyWireASLINK system and turn ON the
power.
AnyWireASLINK system.
error and assign an address different
from the address of that unit.
connected to the same
AnyWireASLINK system.
the ASLINKAMP and the master unit
shorter.
LINK
LINK
IN
ALM