[Monitor display]
Displays the operation status of this product using the LEDs.
Normal state: LINK flashing, ALM off, IN ON on/OFF off
Name
Indication status
Transmission error,
On
I/O power supply voltage reduction
LINK
Both the transmission signal and
Flashing
24V power supply are supplied
(Green)
Off
No power supply
I/O power supply voltage drop,
On
Sensing level drop
ALM
Slave unit voltage drop
Flashing
(including DP, DN disconnections and reverse connections)
(Red)
Off
Normal
Alternate flashing
LINK
Master unit detecting that the unit ID (address) is
LINK
ALM
redundant or not set
ALM
On
IN
ON
(Orange)
Off
OFF
LED display
7-segment display
Threshold display
The display is the same for both the base unit and the extension unit.
[Troubleshooting]
When the following errors are indicated on the display window of this
product, take measures as shown below.
LINK
IN
ALM
○
○
○
Off
Off
Off
●
○
○
On
Off
Off
◎
○
◎
Flashing
Off
Flashing
(0.5 seconds
(0.5 seconds
alternately)
alternately)
-
-
◎
Flashing
(On for
0.2 seconds,
off for
1.0 seconds)
■Unit voltage (DP-DN) reduction detection
Flashing
The display is the same for both the base unit and the extension unit.
Check the following points and remove the corresponding cause.
- Is the voltage of the 24V DC power supply supplied to the AnyWireASLINK
master within the allowable voltage range?
- Is there any looseness or poor contact in the connections between the main
line and branch lines?
- Do the unit and connection load currents meet the system conditions?
Details
LINK
IN
ALM
Light receiving level value display
LINK
IN
ALM
Cause
Measures
- AnyWireASLINK
- Con rm that there is no disconnection
transmission signal
between the ASLINKAMP and the
is not connected.
AnyWireASLINK system, and recover
- Power supply for
the connection.
the AnyWireASLINK
- Con rm the power status of the
system itself is not
AnyWireASLINK system, and turn on
turned on.
the power.
- Transmission waveform
- Re-connect to the AnyWireASLINK
cannot be received due
system.
to reasons such as the
DP-DN line being
directly connected to
the 24-0V power supply.
- The ASLINKAMP
- Set any address other than 255.
maintains the
address 255
(default setting).
- The ASLINKAMP has
- Look for the other unit which has the
an address redundant
same error indication, and set any
with another unit.
address different from it.
- The internal power
- Decrease the number of units
voltage of the
connected to the same
ASLINKAMP has been
AnyWireASLINK system.
reduced.
- Shorten the transmission line between
- DP-DN disconnections
the ASLINKAMP and the master unit.
and reverse connections
LINK
LINK
IN
ALM
ALM
LINK
IN
ALM
■Error voltage detection
If the 24V DC voltage supplied to this unit is signi cantly reduced (near
approx. 16V), "dc24 Lo" is displayed and the unit's functions stop.
Con rm the supply voltage and bring it within the allowable range.
When the following error is indicated on the address writer, take
measures as shown below.
Indication
Cause
[E-0303]
The set parameter is
incorrect.
Take measures as follows in the following case.
Symptom
Detection cannot be
performed.
Setting cannot be
performed with
ARW-04.
[Parameters and items]
Parameter
Variable
[01.]
Threshold
(0 - 100%)
[02.]
Hysteresis
(0 - 100%)
[03.]
Alarm value Hi
(0 - 100%)
[04.]
Alarm value Lo
(0 - 100%)
[05.]
Alarm value
monitor time
[06.]
Light ON/Dark
ON
[07.]
Operation
mode
[08.]
Light receiving
level display
[09.]
Light emitting
power
[10.]
ON Delay
[11.]
OFF Delay
[12.]
One Shot
[17.]
Address/
Parameter
automatic
setting
(Base unit only)
[18.]
7-segment
display
orientation
switch
(base unit only)
-L*F1011 9/11-
Measures
Check the parameter correspondence table and set
the correct parameter.
Measures
- Is wiring correct?
→ Recon rm the transmission line and power supply line connections.
- Is power fed to the AnyWireASLINK system?
→ Con rm the power supply.
- Has address setting been performed?
→ Perform address setting.
- Are you using within the rated input range?
→ Use within the rated detection range.
- Is wiring correct?
→ Recon rm the transmission line connection, and that the transmission signal is
applied.
- Is power fed to the AnyWireASLINK system?
→ Con rm the power supply.
- Was setting performed with the protective cover open?
→ Open the protective cover. Setting cannot be performed with the cover closed.
- Is the set parameter correct?
→ Check the parameter correspondence table and set the correct parameter.
Details
0-4095
Set the light receiving level value to judge detection.
0-4095
Set the amount of change in the light receiving value
required to turn the detection state from ON to OFF.
0-4095
Set an upper limit for light received to generate
an alarm.
0-4095
Set a lower limit for light received to generate
an alarm.
3-255
Set a monitor time of light receiving value to generate
an alarm. (1 = 100ms)
0
Transmission type dark (shielding) ON
1
Transmission type light (transmission) ON
2
Re ection type dark (w/o re ection) ON
3
Re ection type light (w/ re ection) ON
0
Simple mode (Preventive maintenance function disabled)
1
Normal mode (Preventive maintenance function enabled)
0
AD value display (0 - 4095 Digit)
1
0 - 100% display
0
High
1
Middle
2
Low
0-999
Set the ON delay time. (1 = 100ms)
0-999
Set the OFF delay time. (1 = 100ms)
0-999
Set the One Shot time. (1 = 100ms)
0
Automatic setting disabled
1
Automatic setting for address only
Automatic setting for parameter only
2
* Linked to base unit's parameters.
3
Address/Parameter automatic setting
0
Normal display
1
180° ipped display
Default variable
50
5
0
0
50
0
0
0
0
0
0
0
0
0