スイッチ 3P Technik TCS5JBLのPDF 設置および操作マニュアルをオンラインで閲覧またはダウンロードできます。3P Technik TCS5JBL 6 ページ。 Low-voltage top-up switch
Description Of Operation
The TCS5JBL Low Voltage Top-up Switch is intended to ensure the availability of water in a tank by
topping up the tank when the level becomes low, with a measured amount of mains water.
Water level in the tank is sensed via a float switch, and top-up of mains water is achieved via a
solenoid valve connected to the mains water supply.
The solenoid will be activated when the float switch reaches a downward angle of approx 45deg or
more, the top-up cycle will then continue until the float switch reaches an upward angle of approx
45deg, thereby ensuring a measured quantity of water is introduced to the tank and avoiding
unnecessarily frequent top-ups.
The float switch and solenoid circuits are both powered by a safe low-voltage, either 24Vdc
(TCS5JBL) or 24Vac (TCS5JBLA) with limited current and over-voltage protection.
Installation
Safety Precautions
Mains Voltage – There are exposed electrical conductors inside this appliance. This appliance must
be installed and serviced by a competent electrical technician to the current requirements of
BS7671 and IEEE recommendations. Before servicing this appliance, normal safe isolation
procedures should be implemented.
Do not touch any connection terminals while energised.
Do not attempt to service this item when wet, or in a wet or high humidity environment.
If the housing of the control panel becomes damaged, you must shut down and securely isolate
this appliance immediately.
Included Components
TCS5JBL/TCS5JBLA Series Control Unit
2 x Male Connecting Plugs
Layout
The control panel can be mounted indoors or in sheltered outdoor locations (barns, covered areas,
etc). It is rated at IP66 and will not withstand persistent and direct rain, immersion, etc.