PLC Output Card or External Relay
Notes:
1. All System Inputs share the same Isolated Common (J2-13).
to the positive supply or ground.
2. Dukane's current limited power supply can be substituted for the +24Vdc supply above. Connecting +22Vdc
(J2-1) to Isolated Common (J2-13) would allow a dry contact closure between any System Input and 0V Return
(J2-2). Connecting the System Inputs in this way would be similar to activating DPC series System Inputs.
Warning: Any connection to the Ultrasound Activation/Cycle Start Input (J2-8) or the Automation Thruster Control Input
(J2-9) should be disabled during an emergency stop condition.
AN502 (REV 07)
Page 6 of 16
Connecting a Relay Contact Closure
PLC Digital Outputs
Sinking Current
0Vdc Return
APPLICATION NOTE
iQ System Inputs
+24Vdc Supply
(+30Vdc max)
Isolated Common
J2-13
iQ Digital Input
Sourcing Current
It is critical that the isolated common is connected
AN502