- ページ 15

浄水器 AOM EANのPDF 仕様をオンラインで閲覧またはダウンロードできます。AOM EAN 20 ページ。 Electrostatic filters

AOM EAN 仕様
7.8.7
EAN ESP unit installed in a ceiling space and requiring physical presence inside the ceiling space to be serviced.  
This implies that the EAN unit is positioned away from the access panel to a point where the service technician needs 
to physically enter the ceiling cavity to service the machine.  
The access panel to the ceiling space needs to meet the above requirements.  
A secure access path needs to be guaranteed between the access panel and the EAN ESP unit.  
A secure working platform needs to be placed in front of the unit.  
7.8.8
EAN ESP unit installed along an open duct, either indoors or outdoors.  This generally implies that the EAN ESP units 
are visible and are located at a certain height that may require the use of a removable working platform (type scissor 
lift).  The available space directly below the EAN ESP unit doors needs to ensure that a safe working platform can be 
installed in order to service the units.  
7.8.9
EAN ESP unit installed in a plant room.  An access path from the plantroom entry point to the EAN ESP unit door of a 
minimum width of 1 m and the minimum door maintenance space in front of the ESP unit's door as shown in the above 
figures need to be guaranteed. Should the plantroom be located above level 1, an access lift is recommended in order 
to decrease the time required for servicing.    
7.8.10
EAN ESP unit installed on a rooftop. The overall access from the building entry point to the EAN ESP unit needs to 
follow the previous recommendations. Access using vertical ladders should be limited to a maximum of 1.5 m in 
height, since a service technician will need to carry clean and dirty ESP cells weighing between 10‐15 kg.  
 
7.9
Electrical connection 
 
 
Warning: Though the EAN ESP unit is a plug in and play, it is recommended that the overall electrical installation be carried out 
by a licenced electrician.  
 
 
7.9.1
Plug the generator electrical lead to a 10 amp circuit power point.  
7.9.2
The power point should be interlocked with the fan switch. When the exhaust fan switch is activated, the voltmeter 
should indicated 240 Volt.   
 
21/54 Beach Street Kogarah NSW 2217     Tel Sales 1300 903 788     Service 1300 904 088 
rev 1, 22/09/2016 
 
 
 
AOM AUSTRALIA 
www.aomaus.com.au    email [email protected] 
 
 
 
 
 
 
 
 
 
 
15