It is essential that the End User be made aware of the O&M requirements related to the EAN ESP unit.
If the red LED indicator light switches on systematically between cleaning regimes the cleaning schedule should be
adjusted accordingly.
8.2.4
As soon as the red light illuminates, the unit cell needs to be cleaned. If the EAN ESP unit is not visible, AOM proposes
a remote indicator that can be installed in the kitchen and linked to the EAN units.
8.2.5
When cleaning the AOM equipment, do not use caustic chemical. The chemical could damage the aluminium ESP cell.
8.3
Troubleshooting
Note: All trouble shooting should be performed by qualified personel and extreme caution should be used when working on the
EAN ESP unit electrical boards.
Problem: The EAN ESP unit does not power ON (no green LED light/ no voltage)
Have the electrical connections including the fan
interlock been done as per AOM specifications?
If 240 V power reaches the unit, is the fuse continuity
on the PCD assured (red light on the PCB)?
Problem: The EAN ESP unit powers ON but the amperage fluctuates and does not settle to a fixed amount
Has the unit been properly cleaned and/or is the red
LED light showing on the door?
Have the cells been removed and replaced within the
unit?
Problem: The EAN ESP unit powers ON but the amperage fluctuates and does not settle to a fixed amount – an electrical
discharge can also be heard within the unit.
Have the cells been removed and replaced within the
unit?
Has a cell been damaged?
Problem: The EAN ESP unit powers ON but no amperage is shown on the amperemeter
Was this observed before or after the changeover of
electrostatic cells?
21/54 Beach Street Kogarah NSW 2217 Tel Sales 1300 903 788 Service 1300 904 088
rev 1, 22/09/2016
Check 240 V power reaches the unit when the fan is switched ON
If not, replace the fuse
If yes, the issue is with the PCB which is faulty and needs to be
replaced.
The EAN ESP unit needs to be cleaned as the buildup of grease and
other contaminants has affected the electrical connections of the
unit.
If yes, the connections between the EAN unit and the cell, as well as
between the cells need to be checked as follows:
‐ The EAN ESP unit insulators situated on the door are free from
grease
‐ The cells are equipped with the required springs and gaskets and
all the connections are ensured.
If yes, the cells need to be checked for any visible damage,
particularly in the case where aluminimum plates are bent and
touching.
If yes, attempt to fix any mechanical damage to the cells or replace
the cell with another clean cell.
If after, one of the cells has a fault. Remove the cells and review the
cells including checking that the the high voltage wires are all
attached.