- ページ 20

コントロールユニット Dungs FRSBV 20010 HDのPDF ユーザーマニュアルをオンラインで閲覧またはダウンロードできます。Dungs FRSBV 20010 HD 20 ページ。
Dungs FRSBV 20010 HD にも: 取扱説明書 (20 ページ)

Dungs FRSBV 20010 HD ユーザーマニュアル
Safety-relevant components
Valve test systems
Gas pressure controller
Air pressure monitor
Gas failure switch
Combustion manager
UV flame sensor
1
Gas pressure regulators
Gas valve with valve test system
Gas valve without valve test system
Control system for gas and air supply
Decreasing performance on account of ageing
1
Gas families I, II, III
2
N/A
not applicable
Subject to technical modification in the interest of technical progress.
Headquarters address:
Karl Dungs GmbH & Co. KG
Karl-Dungs-Platz 1
D-73660 Urbach,
Germany
Telephone  +49 (0)7181-804-0
Telefax 
+49 (0)7181-804-166
Internet: www.dungs.com
The
Pressure
Equipment
(PED) and the Directive on the energy
performance of buildings (EPBD) require
a regular inspection of heat generators
to guarantee a high degree of efficiency
long term and minimum environmental
impact as a result.
1
2
2
Subsidiary
Karl Dungs, S.L.U.
Av. Can Roqueta 15
Pol. Ind. Can Roqueta
E-08202 Sabadell,
Barcelona / Spain
Telephone  +34-935647550
Internet: www.dungs.com
Directive
It  is  therefore  necessary  to  replace 
safety-relevant  components  once 
their service life has elapsed.
Design related operating life
Cycle number
Time duration
250 000
50 000
250 000
N/A
250 000
N/A
operating hours
N/A
After error detected
50 000-200 000
Depending
on the diameter
N/A
CEN standard
[years]
10
EN 1643
10
EN 1854
10
EN 1854
10
EN 1854
EN 298 (gas)
10
EN 230 (oil)
10 000
EN 88-1
15
EN 88-2
EN 1643
10
EN 161
EN 88-1
10
EN 12067-2
---
20 ... 20