- ページ 11
コントロールユニット Danfoss EKE 1PのPDF ユーザーマニュアルをオンラインで閲覧またはダウンロードできます。Danfoss EKE 1P 16 ページ。 Stepper valve extension module, adap-kool refrigeration control system
User Guide | Stepper Valve Extension Module, Type EKE 1P
Alarm list
Alarm text
Valve configuration error
No valve configured
Battery critical low voltage
Battery low voltage
Standby mode
Manual control
Check valve step mode vs
positioning
Valve speed too fast
Valve speed to slow
Valve emergency speed too fast
Valve emergency speed too slow
Valve start speed too slow
Valve short circuit or driver too
hot
Low supply voltage
Network master missing (CAN)
ERR31
© Danfoss | DCS (vt) | 2020.03
Description
One or more valve configuration errors are blocking operation of stepper valve.
Check the other active alarms to identify the valve configuration problem.
No valve selected. Please configure the correct valve.
Voltage from back-up module is found to be critically low and the valve will likely not be fully closed in case of a
power failure.
Check connections / replace battery or EKE 2U module.
Voltage from back-up module is found to be too low to close the valve in case of power failure.
Replace battery or EKE 2U module.
The controller is in standby due to the Main switch parameter setting being off.
The controller is in manual control, no automatic control is active and many alarms are disabled.
With I064 Valve step mode set to "full" and I029 Valve step positioning set,
Half step operation is possible. Correct either I029 or I064.
Number of micro steps/sec is too high (higher than 12800 micro step/sec):
Reduce valve speed or use less micro steps per full step.
Number of micro steps/sec is low (lower than 8 micro step/sec), increase valve speed, increase valve start speed or
use more micro steps per full step.
Number of micro steps/sec is too high (higher than 12800 micro step/sec).
Reduce valve emergency speed.
Number of micro steps/sec is low (lower than 8 micro step/sec). Increase valve emergency speed.
Number of micro steps/sec is low (lower than 8 micro step/sec). Increase valve speed, increase valve start speed or
use more micro steps per full step.
Valve driver is unable to drive valve.
Check for short circuit of the coils or if ambient is higher than 60 °C.
Supply voltage is found to be lower than expected tolerance.
No communication possible with the pack controller AK-PC in application 1. Check the CANBUS connection and
configuration in both EKE 1P and AK-PC.
See next page
BC320219567793en-000201 | 11