• Do not
use
inhibitors
or other
2.
additives
that are not specifically
approved
for this product.
• Consult
a local water treatment
specialist
for
recommendations
if any of the above
are outside
the stated ranges.
3.
Cleanin
tht_tb__vdronic S_stem:
IMPORTANT:
Do not mix dif-
ferent
manufacturers'
prod-
ucts.
Doing
so
will void
the
warranty
of the boiler.
Consideration
should
be
given
to cleaning
the
heating
system,
particularly
in
retrofit
situations
where
a new
boiler with an alu-
minum
heat
exchanger
is being
installed
in an existing
piping sys-
tem. Systems
that have antifreeze
that is not approved
by the boiler
manufacturer
must be completely
flushed
to ensure
no unapproved
antifreeze
remains
In older systems
obviously
discol-
ored, murky or dirty water;
or a pH
reading
outside
the boiler
manu-
facturer's
stated
acceptable
range
are
indications
that
the
system
should be cleaned
or treated.
1. Measure
total
capacity
of the
system
including
the
piping,
tanks,
boiler,
collector
plates,
etc. The most accurate
method
of measuring
fluid capacity
is
to fill the system and then com-
pletely
drain
it, volumetrically
measuring
the fluid drained.
Thoroughly
flush
the
system
with
clean
water
to
remove
any sediment
or contaminants.
Sludge and iron oxide deposits
can cause rapid breakdown
of
inhibitors.
Cleaning
fluid - Flushing
with
clean
water
is preferred.
If
cleaning
fluid
is used,
only
use
cleaner
specifically
ap-
proved
for
use
with
alu-
minum
boilers.
Utilize
the
cleaner
in
accordance
with
manufacturer's
instructions.
Freeze
Protection
Aluminum
Safe Antifreeze,
Treat-
merits and Additive
Guidelines:
Antifreeze,
if needed,
must be of a
type specifically
designed
for use
in closed hydronic heating systems
and be compatible
with type 356
T6 aluminum
at operating
temper-
atures between
20°F (-6.7°C)
and
250°F (121 °C). See the "Approved
Aluminum
Antifreeze
& Inhibitor
Suppliers"
section
of this manual
for a list of boiler manufacturer
ap-
proved products.
• Always clean system
prior to us-
ing antifreeze,
refer to the Clean=
ing the Hydronic
System
section
of this manual for details.
• Only
use the antifreeze
manu-
facturers'
products
outlined
in
this document.
• Use of antifreeze must be in accor-
dance with local plumbing codes.