In case of alarm
Extinguish any naked flames.
Do not switch lights or electrical devices on or off.
Open all windows and door to increase ventalation.
If the ALARM LED is off the levels of gas have dropped. A responsible, qualified person is now safe to find the cause of the alarm.
If the alarm sound reamins constant and the cause is not evident or not possible to eliminate turn off the emergency isolation valaves to the area and
contact your gas provider emergency line. They will advise accordingly.

Troubleshooting

The Problem
The BX150 does not start up
The Fault LED is illuminated
The Overload Sensor LED is illuminated
The Overload Battery LED is illuminated
The BX150 is repeatedly issuing an alarm
The BX150 is issuing an alarm and does not
shut off the devices connected to it
A 12V solenoid valve, which does not work
well, is connected to the BX150
Still experiencing difficulties?
If you have made the checks above and are still experiencing diffculties then please call Duomo (UK) Ltd on
+441905 797989
for technical assistance.
t: 01905 797989
e: [email protected] | w: www.duomo.co.uk
Check that the 230V mains power is correctly connected. If powered by the battery, check that the
12V DC power is correctly connected.
Check that the connecting cables from the BX150 to the sensors are intact, that the sensors are
properly powered and that the signal cable is correctly
connected.
Check that;
The power polarity has not been inverted
No short-circuit is present
The probes were not damaged during installation, that no excessive current absorption is
present
Check that the connection cables are not shortcircuited, that the polarity has been inverted and the
battery is not damaged.
Check that there are no gas leaks
If the alarm signal and the fault indicator LED turn on together, check the sensor.
Check that the wiring is correct and that the DIP switch has been set properly. All relays must be
free from electrical powe. Check the drawing of the connections.
Direct connection of 12V solenoid valves or sirensto the BX150 is not permitted. An external power
unit must always be used. The BX150gives a maximum current of 50mA.
9