- ページ 2
スイッチ DANLERS CESRAPIRSDのPDF インストレーション・ノートをオンラインで閲覧またはダウンロードできます。DANLERS CESRAPIRSD 2 ページ。 Ceiling surface pir absence switch/dim control (round)
Installation procedure
1. Please read these notes carefully before commencing work.
In case of doubt please consult a qualified electrician.
2. POSITIONING: The CESRAPIRSD should be installed to achieve
correct coverage of the area, see diagram A. If the photocell override
facility is required, the switch must be located above an area where
daylight can give greater illumination than the artificial light. Avoid
locating this product where it is exposed to windy or drafty conditions
(exposed lobbies, open ceiling voids or near ventilation fans) or
near heat sources. To cover large areas CESRAPIRSDs should be
spaced in a 5 metre grid formation.
3. The greatest energy savings will be made if each CESRAPIRSD
controls an independent set of lamps. They can be wired in parallel
but this should ideally be limited to three, see diagram D.
4. Make sure the power is isolated from the circuit. The
CESRAPIRSD should be connected as shown in diagrams C & D:
L - Live in. N - Neutral in. SW
5. Knockout or drill the appropriate holes on the mounting plate for
attaching the plate to the ceiling or back box (if applicable). Feed
cables through the appropriate (side or rear) entry hole. Screw the
back mounting plate to the ceiling or back box via the mounting
holes. Wire the cables into the sensor head block terminal. Push
the sensor head onto the mounting plate and align the side clips
with the slots on the sensor heads.
Start-up mode
When the CESRAPIRSD is powered up, it will switch on the load for 1
minute, the load will then switch off and the CESRAPIRSD will enter
its Operating Mode.
Time and Lux set-up
For convenience, ensure that the TIME is set to the minimum when
setting up the LUX level. Afterwards set the TIME to a value suitable
for the application, making reference to diagram B.
The LUX is best set up when the local ambient light is at approximately
the minimum desired working light level. With the LUX set fully clockwise
wait for the CESRAPIRSD to switch off. Step the LUX adjuster slowly
anticlockwise (- to +), at each position operate the momentary wall
switch and continuing until the lamps switch on.
- Switch input. SL - Switched Line out.
1
A: Detection diagram
For optimum coverage
recommended mounting
height: 2.4 to 5m
up to 5m
up to 7m
B: Adjusting time and lux
Typical settings
2.5m
80s
5m
1000 LUX
40s
10m
20s
20m
10s
40m
30 LUX
PHOTOCELL
INACTIVE
min
max
max
min
TIME
LUX
D: Wiring diagram, multiple CESRAPIRSD's
L
SW
1
L
Mains rated
retractive wall
switch
230 VAC
N
Strong detection zone
i.e. person moving arm
or walking towards PIR
Secondary detection zone
i.e. person walking
perpendicular to PIR
C: Wiring diagram, Single CESRAPIRSD
Switch / DIm
ballast input
L
L
CESFAPIRSD or
SW
1
CESRAPIRSD
L
SL
Mains rated
N
retractive wall
switch
230 VAC
N
Switch / DIm
ballast input
A few
CESFAPIRSD or
CESRAPIRSD
SL
load
load