INSTALLATION
I
nstallation consists of setting the straps and switches, wiring
the connector, and installing the module.
Each of the eight ports of the 46022-12 MAC has an RS-422
data communications interface. If you require a different
interface, connect the serial alarm device through a 46035
Converter Module or a 46022-20 MAC equipped with the appro-
priate interface subassembly.
1. Set the straps.
You can strap the 46022-12 MAC to have its alarm inputs
(receive lines) either terminated or unterminated. The termi-
nating load is 100 ohms. Each alarm port must have a current
path at some point of termination, which is normally set at the
MAC.
♦
If a channel is connected to communications lines, the resis-
tor is normally strapped IN (position B).
♦
If termination for a channel is provided at the source, strap
the resistor OUT.
Refer to Table A and Fig. 2.
2. Set the switches.
A mini-DIP switch (S1) selects the card address, used by the
46020 MAP to sequence all MACs in an alarm system. Refer to
Table B and Fig. 2 to set the switches.
NOTE:
In order for the system to function properly, two MACs cannot
share the same address.
To make any port of the 46022-12 MAC addressable for
interfacing remote discrete alarm points to the shelf without
rewiring, you may use the 46022-12 MAC in conjunction with a
46022-30 MAC.
3. Wire the connector.
Normally the 56-pin edge connector in the shelf is prewired at
the factory. If you are going to wire the connector, refer to Fig. 3
for module connector pin wiring assignments. Wire the connec-
tor in the shelf or housing as required.
4. Install the module in the equipment housing.
46022-12-0299 <90-00008>