INSTALLATION
To check the operation of the 46017 SAAM, monitor the unit in a
system:
1.
Apply an alarm at each input being used and observe the front
panel for proper audible alarm, LED, and relay operation.
2.
Acknowledge the alarms and verify that the audible alarms stops,
the NEW LEDs turn off, and the NEW relays release.
3.
Clear the alarms and verify that the EXIST LEDs turn off and the
EXIST relays release.
OPERATION
F
or the most part, operation of the 46017 Summary Audible
Alarm Module consists of observing the lamps and audible
alarm for alarm indication or operating one of the front panel
Alarm Cut-Off (ACO) switches.
♦
The front panel of the 46017 Summary Audible Alarm Mod-
ule has two LEDs for each alarm input:
• The upper row of LEDs in each alarm group (EXIST) indi-
cates which of the 16 alarm inputs has an alarm present.
• The lower row of LEDs in each alarm group (NEW) indi-
cates an alarm that has not been acknowledged.
ON
♦
You can acknowledge alarms in one of several ways:
• Press the acknowledge (ACK) buttons on the front panel.
• Acknowledge the alarms remotely if the acknowledge in-
puts are connected to a remote ground source.
• Press the EXT ACK button on the front panel if the button
ON
is wired for operation.
• Wait for the alarms to acknowledge automatically if you
are using the time-out function.
ON
♦
To disable the audible alarm, place the bottom ACO switch
ON. The bottom ACO LED will light.
♦
To disable external alarm indicating devices connected to the
module relays, place the ACO switches for groups 1 or 2 ON.
The corresponding ACO LED will light.
♦
To adjust the volume of the audible alarm, rotate the damper
over the audible alarm at the bottom of the front panel.