- ページ 14

コントローラー Dantherm 094838のPDF マニュアルをオンラインで閲覧またはダウンロードできます。Dantherm 094838 20 ページ。

Dantherm 094838 マニュアル
Standard Mode
(Freecooling <> A/C)
14
Default Cooling strategies,
Description
Off
Temperature when fan stops
On
Temperature when Fan starts
Min °C
Temperature at bottom of P-band
Max °C
Temperature at top of P-band
The wanted indoor temperature; fan speed will be adjusted between
Set Point
Min°C and Max °C
A/C 1 on
External Air Con unit 1 start if connected
A/C 1 off
External Air Con unit 1 stops if connected
A/C 2 on
External Air Con unit 2 start if connected
A/C 2 off
External Air Con unit 2 stops if connected
Emergency on
Fan run 100% and both A/C 1 and A/C 2 starts
Emergency off
Fan stops both A/C 1 and A/C 2 continue to run
A/C unit 1 start at set point if outdoor temperature is less than 3°K colder than set point.
If outdoor temperature is more than 3°K colder than setpoint the A/C unit 1 will start at 31°C
continued
Value
20
23
25
29
27
31
29
33
31
38
36