- ページ 4

産業機器 Dantherm Cooling HEXFLOW PINNACLE SeriesのPDF 製品情報マニュアルをオンラインで閲覧またはダウンロードできます。Dantherm Cooling HEXFLOW PINNACLE Series 14 ページ。

Dantherm Cooling HEXFLOW PINNACLE Series 製品情報マニュアル
Dantherm Cooling , Inc. Heat Exchanger Operating & Maintenance Manual

3. MODEL IDENTIFICATION

Model numbering format
3.1.
Pinnacle
S = Standard
X = Custom (further nomenclature invalid)
Nominal Height
018 = 18"
023 = 23"
035 = 35"
060 = 60"
Capacity
017 = 17 W/ºF
022 = 22 W/ºF
026 = 26 W/ºF
035 = 35 W/ºF
045 = 45 W/ºF
055 = 55 W/ºF
100 = 100 W/ºF
Voltage:
A = 115 volt / single phase
B = 230 volt / single phase
Y = 24 VDC
Z = 48 VDC

Options:

-GR
-L
-M
-PXX
-S
-T1
4. OPTIONS
Speed Control (-S)
4.1.
The controller is designed to slow down the speed of the internal and external fans at lower
temperatures to reduce noise and energy consumption. It will also supply either a normally closed
(NC) or normally open (NO) alarm signal for fan fault, sensor fault, or high temperature.
Thermostat Control (-T1)
4.2.
A snap disc thermostat controls the operation of the external loop fan. A temperature rise above
80F will cause the fan to be turned on, a temperature decrease below 60F will cause the fan to be
turned off; between the range of 60F-80F the fan will be operating based on the pervious
environmental condition experienced.
HexFlow Pinnacle Series Product Information Manual
= Additional Environmental Protection
= External Plug
= Stainless Steel Cover
= Non Standard Paint Color
= Speed Controller
= External Fan Thermostat
P S 035 035 Z – T1
Page 4 of 14