- ページ 10
エンジン Belimo FS SeriesのPDF 交換をオンラインで閲覧またはダウンロードできます。Belimo FS Series 19 ページ。 Replacement of multiproducts motors
Belimo FS Series にも: 取扱説明書 (20 ページ), インストラクションシート (18 ページ)

- 1. Table of Contents
- 2. Code and Standard Issues
- 3. NFPA 80 (Fire) & NFPA 105 (Smoke )
- 4. Local Code Approval
- 5. Cross Reference
- 6. Fire & Smoke Damper Technical Details
- 7. Replacement Instructions
- 8. Mounting Methods
- 9. Linkage Mounting
- 10. Miscellaneous Parts
- 11. Thermal Sensor Replacements - BAE165 US
- 12. Auxiliary Switches
- 13. Wiring
- 14. Building Official/Fire Marshal Notification Form
Mounting Methods
Short Shaft Mounting
The Belimo clamp is very stable
when mounted between the actuator and
the supporting sheet metal.
After mounting, tighten the clamp
nuts with a 10mm, long-nosed, deep-well,
¼" drive socket.
Actuators are mounted on the sleeve of the damper
some cases with a remote sensor and sometimes
within the sheet metal bracket shown below.
Belimo FSLF anti-rotation strap (yellow arrows). Shaft
adaptors and other mounting plates are available.
In all cases, the stud of the anti-rotation strap should fit in the middle of the slot at the bottom of the
Belimo. This allows the actuator to move as necessary to compensate for any non-concentric
rotation of the damper shaft.
Air Balance Honeywell ML&MS Types to Belimo FSxx
Typical External Mount
Note: short shaft.
For small dampers where the
actuator must hang out in the air.
bracket
in
Alternatively,
reuse old
bracket
Bolts and
lock nuts.
Old
AF-P anti-
rotation strap.
Score and
break off
excess.
March 2018
10