- ページ 7
ゲートウェイ Belimo UK24MODのPDF 製品情報をオンラインで閲覧またはダウンロードできます。Belimo UK24MOD 20 ページ。 Mp to modbus rtu
UK24MOD
Electrical installation
With DC 24 V supply:
Calculation of the maximum signal
conductor lengths
To be read out from the mass of curves:
For cables with wire-Ø
Cable length
[mm²]
0.75
1.00
1.50
2.50
Dimensions
Dimensional drawings [mm]
www.belimo.com
Belimo Gateway MP to Modbus RTU
(continued)
The power consumption [W] of the MP/MPL/MFT(2) actuators used is to be added, and the
corresponding signal conductor lengths are to be read from the diagram.
Example:
The following is connected to the MP-Bus: 1 pc. NM24A-MP, 1 pc. SM24A-MP, 1 pc. LMV-D2-
MP.. and 1 pc. NV24A-MP
Total power rating 3.5 W + 4 W + 3 W + 3 W = 13.5 W
[m]
55
75
110
190
T9-UK24MOD • en • v1.7 • 02.2014 • Subject to changes