Figure 6: Openings for through Floor / Wall / Roof Models
Opening required when installing the Models DAS1, DIS1, DIS2,
DIS4 throught a roof, floor or wall made of combustible materials.
DAS1, DIS1, DIS2, DIS4 made of combustible material
Figure 2 - Opening for Models
Grease Duct – UL1978
Minimum Square OPENING for NON-Fire Rated Floor / Wall /
Roof for different Models
Duct
Flue
Model
Diameter Ø
Combustible
(in.)
Roof / Floor /
DCL
5 to 36
ID + 37 1/4"
5
ID + 8 3/4"
6 to 11
ID + 10 3/4"
12 to 16
ID + 12 3/4"
DAS1
18 to 22
ID + 14 3/4"
24 to 28
ID + 16 3/4"
30 to 34
ID + 18 3/4"
36
ID + 20 3/4"
5 to 13
ID + 4 3/4"
14 to 24
ID + 6 3/4"
DIS1
26 to 34
ID + 8 3/4"
36
ID + 10 3/4"
5 to 16
ID + 2 3/4"
DIS2
18 to 30
ID + 4 3/4"
32 to 36
ID + 6 3/4"
5 to 16
ID + 2 3/4"
DIS4
18 to 30
ID + 4 3/4"
32 to 36
ID + 6 3/4"
5 to 9
DIS3Z
ID + 6 3/4"
10 to 36
Table 2: Openings for through Floor / Wall / Roof – NON-Fire-
Grease Duct – UL1978
CIXPRO SERIES FOR GREASE DUCT UL1978 SUBMITTAL RECORD
DAS1: 0 8 = 0A + 2
DIS1: 08 = 0A + 2
DIS2: 08 = 0A + 4
DIS4: 08 = 0 A + 8
C = 0 B + 3/4
D = C + (2 x Clearance)
See Table for
Opening Dimensions
Outer Band (BSE)
For Models DAS1, DIS1, DIS2, DIS4
Floor
INNER WALL
DCL, DAS1, DIS1, DIS2, DIS4)
OUTER WALL
( DAS1, DIS1, DIS2, DIS4 )
Insulation (Air or Fiber Wool)
DIS PRO
Through
Through
Non-Combustible
But NOT-FIRE-
Wall (in.)
RATED
Roof / Floor / Wall
(in.)
ID + 1 1/4"
ID + 2 3/4"
ID + 2 3/4"
ID + 4 3/4"
ID + 8 3/4"
ID + 6 3/4"
Rated
CLEARANCE TO COMBUSTIBLE FIRE
RATED
UL 2221
Model DIS3Z is equivalent to a 2 – Hour fire
rated grease duct enclosure system.
DIS3Z is "0" inch clearance to combustible
CLEARANCE TO COMBUSTIBLE (from the outer band -
DIS3Z – 5" TO 36"
Table 3: DIS3Z Clearance to Combustible
Model DIS3Z may penetrate a combustible floor, wall or roof
using the appropriate parts and opening sizes. Refer to the
installation instructions for detailed information.
Whenever the DIS3Z grease duct passes through a fire rated
wall or floor, a DIS3Z Ø TPFK must be used to maintain the
fire rating.
Fire resistance rating: 2 hours (F & T)
FIRE RATED (2-HR) FLOOR PENETRATION
Fig. 7: Through Penetration Firestop fire-rated Floor
Penetration
NOTE:
Must use S-TPFS (Spec Seal Triple S Intumescent
Firestop Sealant – SSS100). Ordered separately
from DIS3ZØTPFK based on duct diameter. Refer
to table 4 for tube coverage.
REV: 0
AUGUST 2017
BSE)
O"
5
5