5. Return to the roof with the storm collar and termination cap. First install the storm
collar around the exterior of the flue section extending above the roof flashing.
Tighten and slide down over the top of the roof flashing, secure and seal. Install the
termination cap as per manufacturer's instructions. See FIG 7.
WARNING: DO NOT SEAL VENTILATION OPENINGS ON THE
ROOFTOP FLASHING.
IMPORTANT: If an exposed portion of chimney is greater than 5' above the roof line,
use support wires to keep chimney secure. The support wires may be attached to the
outer pipe of the chimney with screws, but must not penetrate the inner flue pipe.
ELBOW INSTALLATION
1. To achieve desired offset you may install combinations of 12", 18", and 48" lengths of
double wall pipe between the elbows.
2. Chimney weight above offset rests on return elbow. Straps must be securely nailed to
rafters, joists, or stud.
3. Maximum length of pipe between supports (return elbow) is 6' of angled run, after
first set of elbows.
NOTE: All pipe joints between offsets shall be secured
with two screws, only on the outer pipe, and must not
penetrate the inner stainless. See FIG 6.
FIRESTOP SPACERS
Firestop spacers are required at each point where the
chimney penetrates a floor or ceiling joist space. Their
purpose is two-fold: they establish and maintain the
required clearance between the chimney and combustible
materials, and they also provide complete separation
from one floor space to another floor or attic space as
required by most codes. When penetrating a floor or
ceiling at an angle, the appropriate approved firestop
should be used. See FIG 8.
When the double wall chimney passes through a framed
opening into an attic space, the firestop must be place in
the attic floor. See FIG 9a.
When the double wall chimney passes through a framed
opening into living space above, the firestop must be
placed onto the ceiling from below. FIG 9b.
10-FOOT RULE
All chimney terminations must extend a minimum of 3'
above the highest point where it passes through the roof
and must be at least 2' above the peak of the roof if within
a horizontal distance of 10' from the peak. See FIG 10.
FIG 9a
FIG 10:
10
FIG 8
FIG 9b
10 foot rule