- ページ 13
安全装置 Apogee Instruments TS-220のPDF オーナーズマニュアルをオンラインで閲覧またはダウンロードできます。Apogee Instruments TS-220 20 ページ。 Fan-aspirated radiation shield
An excitation voltage of 2.5 V DC is recommended to minimize self-heating and current drain, while still
maintaining adequate measurement sensitivity (mV output from thermistor per C). However, other excitation
voltages can be used. Decreasing the excitation voltage will decrease self-heating and current drain but will also
decrease thermistor measurement sensitivity. Increasing the excitation voltage will increase thermistor
measurement sensitivity but will also increase self-heating and current drain.
Measurement devices (e.g., datalogger, controller) do not measure resistance directly, but determine resistance
from a half-bridge measurement, where an excitation voltage is input across the thermistor and an output voltage
is measured across the bridge resistor.
Wiring for EE08-SS
*For more information, please see the EE08-SS manual:
White: Single-ended channel (signal output by
relative humidity sensor)
Green: Single-ended channel (signal output by
air temperature sensor)
Red: Input voltage (7 to 30 V DC)
Black: Ground
Clear: Ground (shield)