In setup mode the volume can be adjusted by holding the magnet adjacent to the fl ashing setup
LED and removing it at the desired volume level. If min or max volume is reached, the confi rmation
LED stops fl ashing. To alter the direction of adjustment, remove the magnet for one second and re-
apply. Saving the volume setting is performed at the control panel.
Please check with panel manufacturer for compatibility of the above setup/test modes.
L1
L2
L1(-)
L2(+)
ON
CIT
1
2
3
4
5
6
7
©Apollo Fire Detectors Limited 2010/EKC
Fig 1. PCB outline
setup LED (red)
polling LED (green)
isolator LED (yellow)
Apollo Fire Detectors Limited 2010/EKC
Fig 3.
Discovery Open Area Voice Sounder
Technical Data
Operating voltage
Switch-on surge
Quiescent current (non-polling)
Alarm current (non-polling) max
Sounder
Visual Indicator
Sounder with Visual Indicator
Alarm power
Sounder
Visual Indicator
Sounder with Visual Indicator
IP Rating
For sound pressure levels measured to EN54–3 see document PP2203
and for isolator operation information see document PP2090,
both available on request.
0
1
1
1
0
0
O
ON = 0
N
1
2
3
4
5
6
© Apollo Fire Detectors Limited 2006-10/DJO/TP/TB
L1(-)
L2(+)
Fig 2. Example of Address 78
confirmation LED (red)
17–28V DC
1.5 mA < 10s
1.4 mA Nominal
9.5 mA
8.8 mA
13.4 mA
266 mW
246 mW
375 mW
21C
2
Individual Address Setting
The address of the Open Area Voice Sounder is set using segments 1-7 of the DIL switch.
Each switch is set to "0" (ON) or "1", using a small screwdriver or similar tool. A complete list
of address settings is shown below.
DIL switch
setting
1
addr 1234567
addr
1
1000000
2
0100000
3
1100000
4
0010000
7
5
1010000
6
0110000
7
1110000
8
0001000
9
1001000
10
0101000
51
1100110
52
0010110
53
1010110
54
0110110
55
1110110
56
0001110
57
1001110
58
0101110
59
1101110
60
0011110
101
1010011
106
102
0110011
107
103
1110011
108
104
0001011
109
105
1001011
110
Fault Finding
No response or missing
Analogue value 1
Analogue value 2
Analogue value 3
Device fails to operate
Analogue Values
Analogue Value
0
1
2
3
4
*Volume 1 does not comply with the requirements of EN54-3
DIL switch
DIL switch
setting
setting
1234567
addr
1234567
addr
11
1101000
21
1010100
31
12
0011000
22
0110100
32
13
1011000
23
1110100
33
14
0111000
24
0001100
34
15
1111000
25
1001100
35
16
0000100
26
0101100
36
17
1000100
27
1101100
37
18
0100100
28
0011100
38
19
1100100
29
1011100
39
20
0010100
30
0111100
40
61
1011110
71
1110001
81
62
0111110
72
0001001
82
63
1111110
73
1001001
83
64
0000001
74
0101001
84
65
1000001
75
1101001
85
66
0100001
76
0011001
86
67
1100001
77
1011001
87
68
0010001
78
0111001
88
69
1010001
79
1111001
89
70
0110001
80
0000101
90
0101011
111
1111011
116
1101011
112
0000111
117
0011011
113
1000111
118
1011011
114
0100111
119
0111011
115
1100111
120
Problem
Possible Cause
Incorrect address setting
Incorrect loop wiring (polarity reversed)
Sounder failed
Visual Indicator failed (Sounder with Visual Indicator
version only)
Sounder with Visual Indicator failed (where visual
indicator exists)
Control panel has incorrect cause
and effect programming
Status
Analogue Value
Flash Memory Fail
17
Sounder Fail
18
Visual Indicator Fail
19
Sounder and Visual Indicator Fail
20
General Fault
21
22
23
3
DIL switch
DIL switch
setting
setting
1234567
addr
1234567
1111100
41
1001010
0000010
42
0101010
1000010
43
1101010
0100010
44
0011010
1100010
45
1011010
0010010
46
0111010
1010010
47
1111010
0110010
48
0000110
1110010
49
1000110
0001010
50
0100110
1000101
91
1101101
0100101
92
0011101
1100101
93
1011101
0010101
94
0111101
1010101
95
1111101
0110101
96
0000011
1110101
97
1000011
0001101
98
0100011
1001101
99
1100011
0101101
100
0010011
0010111
121
1001111
1010111
122
0101111
0110111
123
1101111
1110111
124
0011111
0001111
125
1011111
126
0111111
Status
Sounder Volume 1*
Sounder Volume 2
Sounder Volume 3
Sounder Volume 4
Sounder Volume 5
Sounder Volume 6
Sounder Volume 7