4E-CMP installation and user guide
Device ID
The microphone station needs an ID setting in order to be properly recognized in the network and operate.
If the device ID is duplicated or set to a wrong value, the device will not receive the correct configuration
settings from the master Compact 500 main unit. In this case the remote station will be stuck in its boot
sequence and remain non-operational.
The device ID is set by means of two rotary switches, which define the two-digit hexadecimal value of the
ID.
In order to check or set the Device ID, you must access the rotary switches on the back side of the unit:
1.
Remove the steel plate covering back of the station
2.
Identify the high-significant and low-significant rotary switches. The Device ID is a combination [HI
LO] of those two digits.
3.
Make sure the ID value exists in your configuration settings, relates to the right device type and is
not duplicated on another device. Allowed values: 01-FE
4. Set the Device ID value according to the configuration settings of the Compact 500 system.
5.
Plug-in the L-Net cable connecting the station with the C500 main unit.
6.
Observe the boot sequence which should see the unit automatically entering normal operating
mode afterwards.
7.
Assemble the back plate (and optionally the rubber feet).
Page 7 of 11
HI
LO
4E-CMP bottom view: Device ID setting