PURE 1000●2000●3000
LINE INTERACTIVE SINGLE-PHASE
SINEWAVE
PURE 2000-3000
STEP 1
Remove front
panel

2.3 Ups configuration

STEP 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only.
STEP 2: UPS output connection
There two segments of outputs: segment 1 outlets and segment 2 outlets. Please connect non-critical devices
to the segment 1 outlets and critical devices to segment 2 outlets. During power failure, you may extend the
backup time to critical devices by setting shorter backup time for non-critical devices
STEP 3: UPS connections comunication
Communication port:
With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status
through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP
or AS400 card in the UPS it will provide advanced communication and monitoring options.
STEP 4: EPO connection
Keep the pin 1 and pin 2 closed for UPS normal operation. To activate EPO function, cut the wire between pin 1
and pin 2.
STEP 5: Turn On the UPS
Press the ON button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run
capability during this initial charge period.
STEP 6: Software installation
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
Please use software CD or go to website http://www.megatec.com.tw/Download.htm.
Ver.00 09 March 2018
USB Port
STEP 2
Re-connet battery
wires
RS232 Port
STEP 3
Fix front panel
Intelligent SLOT