BIO-FIGHTER
XL INSTALLATION & OPERATION MANUAL
®
COIL SIZING REFERENCE
INSTALLATION
Determine the dimensions of the coils or
area to be irradiated.
Use the Coil Sizing Reference to determine
the number of lamps needed for proper
coverage.
Larger coils may require multiple Bio-
Fighter kits.
UV LAMP CONFIGURATION GUIDELINES
The distance between UV lamp(s) and the
irradiated surface should be between 6"-
18" is optimal.
The distance between stacked UV lamps
should not exceed 35".
The distance between end to end UV lamps
should not exceed 12".
The distance of UV lamp ends to the edge
of irradiated surface should not exceed 6".
One single lamp can cover 36" of coil
height, 18" above and 18" below. Each
lamp also covers an additional 6" of width
beyond the ends of the lamp, 3" on either
side of the lamp.
12" maximum space between lamps
6" maximum space to end of coils
Overlap lamps where necessary
LAMP SPACING