Description
The P03/3-RS485 Weather Station measures temperature, wind speed and brightness
(eastern, sothern and western sun). It recognizes precipitation and receives the DCF77
radio signal for date and time.
The weather station sends the currently recorded weather data, date and time once
every second. This data flow can be received and analyzed by an end device such as
SPS, PC or MC. If the DCF signal cannot be received, the data is output approx. every
1.35 seconds.
The P03/3-RS485 has four connections. Data output is at terminals A and B. Terminals 1
and 2 are for the power supply (24 V DC). The connections are not resistant to pole
reversal. Connecting them incorrectly will destroy the interface components.
Functions:
Brightness measurement with three separate sensors for east, south and west.
Recognition of twilight/dawn with special filters
Wind speed measurement by means of a nonwearing electronic sensor. No
damage from storm or hail as with mechanical anemometers
Temperature measurement
Heated precipitation sensor (1.2 watts): No false reports as a result of fog or
dew. Dries quickly after precipitation has stopped
Integrated DCF77 radio clock receiver

Technical data

Housing:
Colour:
Mounting:
Protection category:
Dimensions:
Weight:
Ambient temperature:
Operating voltage:
Current:
If switching power supply units are applied, the quality of the radio clock reception may
be influenced.
Data output:
Heating rain sensor:
2
Weather Station P03/3-RS485 • Version: 11.10.2011 • Subject to technical alterations. Errors excepted.
Plastic material
White / translucent
On-wall
IP 44
approx. 96 x 77 x 118 (W x H x D, mm)
approx. 160 g
Operation -30...+50°C, Storage -30...+70°C
24 V DC
max. 125 mA, residual ripple 10%
RS485
approx. 1.2 W