Product description

The Power Supply System KNX PS640 delivers a 29 V bus voltage for the KNX system
and 24 V DC supply voltage for 24 V devices. Special operating conditions such as short
circuit, electrical surge, overcharge or excess temperature are recorded and may be
read off on the display. The present power discharge is displayed as well. It is possible
to reset the connected bus devices directly by means of the key pad.
In addition all functions can be realised via the bus, too, e. g. the transfer of malfunction
messages and operating data and a time/period reset. Malfunction messages are stored
by the KNX PS640+.
Functions:
Delivers a 29 V KNX bus voltage (reduced), output current max. 640 mA, short-
circuit proof
Delivers 24 V DC (not reduced), output current max. 150 mA
Reset of a line directly on the device
Record of operating hours, overload, external overvoltage, internal overvoltage,
short circuit and excess temperature
Display of operating data bus voltage, bus current and temperature of the device
The display may be shown in German, English, Spanish or Dutch
Bus connection for data transfer (e. g. malfunction messages, operating data)
Possibility for reset and diagnostics via the bus
The programme file for KNX software ETS (format VD2) is ready for download on the
Elsner Elektronik website at www.elsner-elektronik.de in the "Service" menu.

Technical data

Housing:
Colour:
Mounting:
Protection category:
Dimensions:
Weight:
Ambient temperature:
Ambient air humidity:
Operating voltage:
Outputs:
Data output:
BCU type:
Plastic material
White
Snap-on fitting on mounting rails
IP 20
approx. 123 x 89 x 61 (W x H x D, mm), 7 width units
approx. 370 g
Operation -5...+45 °C, storage -25...+70°C
max. 95% RH, avoid bedewing
230 V AC , 50 Hz
• KNX bus voltage 29 V (reduced),
Output current max. 640 mA, short-circuit proof
• 24 V DC (not reduced), Output current max. 150 mA
• KNX data
KNX +/- bus terminal plug
Own micro controller