- ページ 12
試験装置 DV Power TRT03のPDF マニュアルをオンラインで閲覧またはダウンロードできます。DV Power TRT03 19 ページ。 Three-phase transformer turns-ratio test instrument
TRT03
4 Error Messages
Any operational error is indicated by a red LED and an additional audio alarm. Furthermore, the display
indicates an error status message. To remove the status message on the display and return to the main
menu, press
.
STOP
4.1 Error Message "Excitation current too high"
This message is displayed if the excitation current exceeds expected values. This value is set to 500 mA.
The excitation current can be reduced by selecting lower test voltages from the device menu.
Figure 4-1:
Error message
"Excitation current too high"
Possible reason for this is the transformer is drawing too much current. In that case, the test should be
repeated with a lower test voltage. Another reason may be the connections are reversed. If there are no
connections errors found, there may be a short circuit within the transformer itself.
4.2 Error Message "Turns ratio too low"
This message is displayed if the turns ratio of the transformer under the test is lower than 0,8. In this case
the user should check whether H and X cables are misplaced (reversed).
Figure 4-2:
Error message
"Turns ratio too low''
4.3 Error Message "Malfunction"
In the case of an internal error, TRT03 will display the massage "Malfunction". In this case, TRT03 device
should be restarted. If the error occurs repeatedly, please contact the DV P
the Section "Manufacturer Contact Information").
Figure 4-3:
Error message
"Malfunction"
4.4 Error Message "Error printer"
This message appears related to a potential problem with the printer. In this case, please contact DV
Support Team (refer to the section "Manufacturer Contact Information").
P
OWER
This message is also displayed if the user tries to print the results from the device which has no built-in
thermal printer installed.
M-T003NN-205-EN
12
Error Messages
Support Team (refer to
OWER