変圧器 DV Power TRT30CのPDF マニュアルをオンラインで閲覧またはダウンロードできます。DV Power TRT30C 19 ページ。 Three-phase transformer, turns-ratio test instrument

TRT30C
Available options in the AUTOTRANSFORMER menu are listed in Table 4.
Config
PH Displacement
Da
displayed
Ya
displayed
Yna
displayed
Za
displayed
Zna
displayed
AVGD
hidden
TRUE 3~ TEST hidden
SINGLE
hidden
Ya, Yna
Da, Za, Zna
If ratio deviation calculation is enabled, the following menu is displayed for entering the name plate voltages
and the tap changer positions:
Figure 3-1:
Input name plate
voltages values
If the name plate voltages are not entered, the TRT30C will perform the test and display the results, but it
will not calculate or display the turns ratio deviation. After the name plate voltages and tap changer
position(s) are entered, press
voltage.
Figure 3-2:
The test voltage
selection
The TRT30C generates both single-phase and true three-phase test voltages. When generating a single-
phase excitation voltage, the TRT30C supplies a single-phase excitation test voltage to each of the three
transformer primary windings in turn. The induced voltages across each of the corresponding unloaded
transformer windings are then measured. The ratio of these voltages is calculated and presented on the
display. It is repeated for all three phases.
M-T030CN-203-EN
Table 4: Available options in the autotransformer menu
Delta winding
Star winding
Star winding with neutral point
Zigzag
Zigzag with neutral point
Automatic vector group
detection
Only true three-phase test
Single-phase autotransformer
Table 5: Available autotransformer vector groups
Configuration
to confirm selection. The next display allows the selection of the test
ENTER
11
Comment
Phase by phase test using
single-phase voltage in turns
or true 3-phase test using 3-
phase voltage, depending on
particular vector group.
True 3-phase test using 3-
phase voltage
Single-phase test using
single-phase voltage
PH displacement
0-4-8
0-1-2,...11
Getting Started
Test mode
High Voltage Tap Changer
position
Low Voltage Tap Changer
position