C) Fail position setting
- User can select the fail position of the actuator in case of control signal failure by adjusting the DIP switches as follows:
NOTE: If not specified, the factory setting of the output signal is 4 - 20mA.
D) Special signal setting for fully open and fully closed
E) Auto setting
This function is used for automatic setting of the PCU card to the predefined limits.
While the actuator is corrected mounted on the valve, check input power, input and output signal connections.
Press ASCAN button once, regardless of the position of the actuator, then the actuator will perform the Auto Setting motion:
1) The blue LED flicker
2) Opening (the red LED flickering) for 5 seconds
3) Pause for 2 seconds
4) Fully closing (the green LED flickering)
5) Pause (the green LED on) for 3 seconds
6) Fully opening (the red LED flickering)
7) Pause (the red LED on) for 3 seconds
8) Moving back to the previous position
NOTE: Since the unit is already set at the factory, no further setting is
required unless the user has adjusted the mounting state of Limit Switch or the Potentiometer.
F) Manual operation
This function allows the user to manually operate the actuator.
To access this function, press the ZERO (black) and SPAN (white) buttons simultaneously for 2 seconds and the yellow LED will be lit to
indicate that the actuator is in Manual Operation mode
Pressing the ZERO button will move the actuator to close and pressing the SPAN button will move the actuator to open
If no operation occurs within 5 seconds, the PCU automatically terminates the Manual Operation mode or alternatively press the ZERO
and SPAN buttons simultaneously for 2 seconds. In either case, the yellow LED will be lit off to indicate the termination of the Manual
Operation Mode.
NOTE: During the manual operation mode, the input signal is ignored.
9
Know-how makes the difference
FAIL CLOSE
Fail Position
Setting
Switch
FAIL OPEN
Fail Last Position
CH 2 Switch
CH 1 Switch
Auto-Full Switch
Open when fail
Close when fail
Auto-Full Switch
(Switch 3) On (up)
Auto-Full Switch
(Switch 3) Off (down)
Signal: 4.3mA
Fully Closed
Signal: 19.7mA
Fully open
Signal: 4.0mA
Fully Closed
Signal: 20.0mA
Fully open
ZERO
SPAN
Button
Button
ASCAN
Button