- ページ 4
ドア開閉システム Cookson Firefly IV MVのPDF オーナーズマニュアルをオンラインで閲覧またはダウンロードできます。Cookson Firefly IV MV 13 ページ。 Release device
INSTRUCTION & DRAWING
1. Actual configuration may differ. Must pull straight cable minimum 18 inches before turning (This
unit may be rotated 90 degrees CW for a vertical pull.). See door manufacturer recommendations
and NFPA 80 for use of this product with specific door. DO NOT install this unit without fusible
links.
2. To be performed by factory authorized personnel only.
3. The release device shall be mounted on a vertical surface with chain end link exiting side of
enclosure as illustrated on figure 1. The unit may be rotated 90 degrees CW for a direct vertical pull.
4. Release device and associated hardware [sash chain or 1/16 cable, eyebolts, fusible links (DO NOT
install this unit without fusible links), turnbuckles] shall be installed as per door manufacturers
recommendations (figure 1 typical installation configuration). Note should be taken that the end link
direction of pull is perpendicular to the enclosure side. An eyebolt installed at a distance of 18 to 24
inches from the release device should adequately redirect sash chain pull as illustrated in figure 1.
Please also see figure 2 for illustration.
Firefly IV MV
Release Device
Figure
3
Firefly IV MV