WIRINg (CONTINUED)
acceSSorY InPUT
Auxiliary Terminal N accepts input signals from load sharing units, auto synchronizers, and other governor system accessories.
GAC accessories are directly connected to this terminal. Terminal N connections must be shielded.
If the auto synchronizer is used alone, not in conjunction with a load sharing module, a 3 Ω resister should be connected between
noTe
Terminals N and P. This is required to match the voltage levels between the speed control unit and the synchronizer.
acceSSorY SUPPLY
Terminal P supplies +10 volt regulated supply to provide power to GAC governor system accessories. up to 20 mA of current can be drawn
from this supply. Ground reference is Terminal G.
A short circuit on Terminal P can damage the speed control unit.
aDDInG a PoTenTIomeTer
use a single remote speed adjustment potentiometer to
adjust engine speed. Select the desired speed range and the
corresponding potentiometer value.
If the exact range is not found select the next higher range
potentiometer. Connect the potentiometer as shown in the
WIRING diagram.
5
ADJUSTMENTS
Before STarTInG THe enGIne
Before starting the engine, check and/or adjust the potentiometer and following settings as desired.

aDJUSTmenT / SWITcH

SPEED
GAIN
STABILITy
DROOP
IDLE
STARTING FuEL RAMP
SPEED RAMP
OVERSPEED
SW1 Lead Circuit
SW2 Soft Coupling

STarTInG THe enGIne

The speed control unit governed speed setting is factory set at approximately engine idle speed 1000 Hz., speed sensor signal).
Crank the engine with DC power applied to the governor system. The governor system should control the engine at a low idle speed. If the
engine is unstable after starting, turn the GAIN and STABILITy adjustments CCW until the engine is stable.
SPeeD ranGe
PoTenTIomeTer / SWITcH
25 turn
270° turn
270° turn
270° turn
270° turn
270° turn
270° turn
25 turn
switch
switch
PoTenTIomeTer
900 Hz
1K
2,400 Hz
5K
3,000 Hz
10K
3,500 Hz
25K
3,700 Hz
50K
facTorY SeTTInG
1470 Hz ± 50 Hz w/ min. trim
50%
50%
0% (CCW)
1075± 75 Hz
100% (CW) Maximum Fuel
0% (CCW) Fastest
100% (CW) Highest
ON
OFF
4
ESD5550-5570 Series Speed Control Unit 1-2021-E1 PIB1003
Governors America Corp. © 2021 Copyright All Rights Reserved
noTeS
Middle position