コントロールユニット GAC ESD5200 SeriesのPDF マニュアルをオンラインで閲覧またはダウンロードできます。GAC ESD5200 Series 7 ページ。 Speed control unit

GAC ESD5200 Series マニュアル
1
INTRODUCTION
The ESD5200 Series speed control unit is designed to precisely con-
trol engine speed with rapid responses to transient load changes. The
ESD5221 is compatible with all GAC proportional actuators except the
ACB2001 electric actuator.
Ruggedly built to withstand all engine environments, the ESD can
control a wide variety of engines in an isochronous or droop mode.
Capabilities include:
Overspeed Switch and LED Indicator
Selectable Droop Operation
Adjustable Idle Current
Auxiliary Accessory Input
Reverse Voltage Protection
Single Element Speed Switch
Speed Anticipation
2
SPECIFICATIONS
Performance
Isochronous Operation
Speed Range / Governor
Speed Drift with Temperature
Idle Adjust Clockwise
Idle Adjust Counterclockwise
Droop Range
Droop Adj. Maximum
(K-L Jumpered)
Droop Adj. Minimum
(K-L Jumpered)
Speed Trim Range
Remote Variable Speed Range
Terminal Sensitivity
J
L
N
P
InPUT / oUTPUT
DC Supply
Polarity
Power Consumption
Actuator Current Range
@ 77°F (25°C)
Speed Sensor Signal
Speed Switch Relay Contacts
Speed Switch Adjustment
Range
ESD5200 Series
Speed Control Unit
± 0.25% or better
1 - 7.5 kHz continuous
±1% MAX
Minimum 1200 Hz below set speed
Minimum 4100 Hz below set speed
1 - 5% regulation
875 Hz., ±75 Hz per 1.0 A change
15 Hz., ±6 Hz per 1.0 A change
± 200 Hz
500 - 7.5 kHz
100 Hz ±15 Hz/V @ 5.0 kΩ Impedance
735 Hz ±60 Hz/V @ 65 kΩ Impedance
148 Hz ±10 Hz/V @1 MΩ Impedance
10 V DC Supply @ 20 mA MAX
12 V DC and 24 V DC Battery Systems
Transient and Reverse Voltage
Protected
Negative Ground (Case Isolated)
50 mA (Continuous plus actuator
current)
10 A Continuous
1.0 - 120.0 V AC
MAX 10 A (N.O. and N.C.)
1000-10000 Hz
reLIaBILITY
Vibration
Testing
envIronmenTaL
Operating Temperature Range
Relative Humidity
Vibration
All Surface Finishes
comPLIance / STanDarDS
Agency
Dimension
Weight
Mounting
1
ESD5200 Series Speed Control Unit 1-2021-C3 PIB1030
Governors America Corp. © 2021 Copyright All Rights Reserved
5 g @ 20 -500 Hz
100% Functional Testing
-40° to 85°C [-40° to 185°F]
5 g @ 20-500 Hz
Fungus Proof, Corrosion Resistant
CE and RoHS Requirements
PHYSIcaL
See Outline Diagram
1.8 lbf [0.82 kgf]
Any position, vertical preferred
up to 95%