parameter.
Fig. 9 – SNMP settings
All the fields in the SNMP group of settings allow a maximum of 31
characters, except "System Description" and "System Location", which
allow 255 characters maximum. The actual content of the page depends
on the SNMP version selected (v1, v2c or v3).
Any changes must be confirmed with the confirm button at the bottom of
the page.
Device status
The Dashboard pageshows the main operating parameters of the
device.
Fig. 10 – Device status
System settings
The System page under Configuration shows detailed information on the
device and installed software, to be communicated to the service
technician if requested. Fig. 11 shows example information: the actual
values will be different.
The "device identification" button allows to locate the CBI60 by emitting
a beep and turning on all leds in sequence.
The "System reset" button allows to reboot the device remotely, only if no
battery connected. Current settings will be maintained. Any changes not
saved with the confirm button will be lost.
"System configuration" and "Manual settings" replicate the settings also
accessible on the CBI60 front panel by pressing the CONFIG button
(refer to the relevant section of this manual). Any changes must be
confirmed with the confirm button at the bottom of the page.
"Battery type" selects the battery chemistry from a drop-down list.
If "Configuration mode" is selected Led 4 ON, the following parameters
(Lifetest, Fast charge, UPS enable and Buffering time) cannot be
changed as they are controlled remotely via Modbus or SNMP.
If "Configuration mode" is not selected Led 4 OFF, the following settings
are available: "Lifetest", "Fast charge", "UPS disable" and "Time buffering
time".
The "Charging current" sets the battery charge current limit.
Via Luigi Barchi 9/B – Reggio Emilia 42124 – Italy
Tel. +39 0522 345518 – Fax +39 0522 345551 –
Fig. 11 – Device settings
Saving the customized parameters
To save the changes into the CBI60 non volatile memory press the
confirm button at the bottom of the page.
How to restore default values in the device
(Customer service)
Resetting the customized parameters to their
default values
In case the login user name or password was forgotten, or the TCP/IP
configuration was set incorrectly and the device is no longer reachable,
please follow this procedure to restore the default settings:
Turn OFF the device
Press the CONFIG button on the front panel and keep it pressed
Turn ON the device and continue to keep the button pressed (all
the 9 configuration LEDs will stay ON during this time)
After 5 seconds the 4 top configuration LEDs (n. 6 to 9) will blink
alternatively in pairs and the LED 1 will blink slowly showing
"Option 1"
Release the button
Now click briefly on the button to select one of 4 options, as shown
by the config LEDs 1 to 4. The options are:
-
1: forces Dynamic (DHCP) IP Addressing Mode
(DHCP) until reboot; the TCP/IP configuration must
be changed on the HTTP server in order to make this
setting permanent.
-
2: system recovery application, only to be used if
instructed by customer service
-
3: restore login credentials, TCP/IP and SNMP
settings to factory default
4: restore the complete device to factory settings –
-
WARNING: all user's settings and logs will be lost,
including the battery type selection.
-
Confirm the choice by keeping the CONFIG button pressed
for 5 seconds until LEDs 6 to 9 stop blinking.

Technical Data

Please Refer to Data Sheet product
www.adelsystem.com
Instruction Manual CBI60_4
Page 5