- ページ 2

モニター ADELSYSTEM DPY351のPDF 取扱説明書をオンラインで閲覧またはダウンロードできます。ADELSYSTEM DPY351 4 ページ。 Monitor and control panel for adelbus network

ADELSYSTEM DPY351 取扱説明書
1
Product Description
The DPY351 is a robust and versatile multifunction display that
allows monitoring, configuring and managing the ADELSystem
devices connected in an ADELBus network. It is equipped with
a high-brightness and wide viewing-angle 3.5'' TFT screen
which guarantees an optimum visibility in any operating
condition. The user interface is clear, intuitive and allows
configuring and managing ADELBus network through its
Ethernet interface by remotely monitoring connected devices,
using the SNMP and Modbus TCP protocols. The configuration
of the Ethernet connection is very straightforward and can be
done by means of the embedded webserver or the intuitive user
interface. The device IP addressing can be static or dynamic
using the DHCP protocol. This makes the connection of a
DPY351 to a LAN very easy. It is possible to connect several
devices in chain together, up to 50.
1.1
Feature
ADELBus network manages all the connected devices.
1.2
Monitoring
It is possible the monitoring of the input and output data, peak
current, peak voltage, all the battery parameters such as
temperature, State of Charge, etc....
1.3
Configuration
With the DPY351, it is possible to modify the parameters of any
ADELsystem device connected: DC Ups, Power Supply and
Battery Charger.
1.4
Alarms management
All the alarms present on the single device are immediately
reported.
1.5
History
The history parameters are recorded inside each device. The
DPY351 allows inspecting all the historical parameters of each
single device.
1.6
Event
Actions that are coordinated among the devices connected can
be programmed, thus automating the system.
2
ADELBus Connections
ADELBus is the ADELSystem network to interconnect the
devices via Modbus and Canbus protocols.
ADELBus is used as power management system for all
connected equipment, such as the DC-Ups, battery charger,
power supply.
Every compatible device with ADELBus is
equipped with one or two data ports. The devices are simply
chained together, forming a local data network. Monitoring
panels such as the DPY351 can be used for monitoring and
control all connected ADELBus equipment.
CAUTION: Never connect a non ADELBus device to the
ADELBus network directly! This will void warranty of all
ADELBus devices connected.
2.1
Event based commands
With ADELBus, a device can be programmed to initiate an
action at another connected device. This is done by means of
event-based commands.
2.2
How to set up an ADELBus network
Connections between the devices are made by standard
straight ADELBus cables. ADELSystem can supply these
cables. These (CAT5) cables are also commonly available at
computer supply stores. For the Can Connection in some
devices it is usual use twisted pair cable with shield.
Up to 50 ADELBus devices can be connected together.
The electric power for the network comes from the connected
devices. Otherwise, if it is not enough it is necessary to connect
the device by + and – connector AUX5.
ADELBus needs a terminating impedance on both ends of the
network, for that it is present a switch termination on the Device.
2.3 Mains Technical Data
Type
Weight
Dimension
Dimension Display
Languages
IP Degree
Power Supply
Power Consumption
2.4 Dimensions
3
Installation
3.1 Panel Mounting
It is possible to mount DPY351 through a 90mm hole on the
Panel and fix them by 4 2.9 x 16. No limit for the Panel thickness.
3.2
How to Supply DPY351
The DPY351 can be powered from the ADELBus network.
There must be ADELBus (AUX3) powering devices available to
provide sufficient power to the network. If there is no ADELBus
powering device or the available power is not sufficient, the
DPY351 must be connected to a 12/24/48 V battery or Output
Load via the supplied connector (AUX5).
3.3 Connection Layout (Fig.1)
1
5
DPY351
0,25 kg.
0.55 lbs.
112 x 116 x 53 mm
4,41 x 4,57 x 2,09 inches
90 mm; 3,5 inches
EN
Front: IP65
Back: IP20
PowerBus/ 12/24/48 Vdc input
Sleep 0,06 W
Normal Mode: 3.6 W
4
2
3
6