Plastic Retainers
Johnson Controls
Panel
Johnson Field
Termination Board
(FTB-102)
to External
Power Supply
Figure 3. InterOp8500/PWRSUP8500 mounted in Johnson Controls panel
10's
Figure 4. Setting the CMnet address
Power Wiring
The InterOP8500 module is designed to
accept power directly from either the
PWRSUP8500 or the existing Johnson power
supply (LPS-105 and RPA-105). In order to
retain the UL listing of your system, a field
inspection is required if using a Johnson
power supply or the RPA-105 and the LPS-105
must be replaced by the PWRSUP8500 or.
Refer to "Using the ALC Power Supply" on
page 6 for wiring with the PWRSUP8500, or to
"Using the Johnson Power Supply" on page 7
for wiring with an existing Johnson power
supply.
Revised 7/10/01 • InterOP8500
Whenever possible, make sure the module's
1's
power and communications connections are
working properly before connecting any
inputs and outputs. Care should be taken to
isolate power wiring from all other wiring
inside the enclosure. The high and low
voltage wiring must be kept as far apart from
each other as is possible to avoid noise
interference.
NOTE To protect analog signals from stray
NOTE
NOTE
NOTE
noise and to minimize EMI, use shielded
cable on all signal wires and low voltage
power wires.
When entering, exiting, or interconnecting
with the enclosure, it is better to use several
small openings than one large one. The 12V
binary outputs are powered by a separate
source supplied through the field termination
board.
CAUTION The InterOP8500 module is a
CAUTION
CAUTION
CAUTION
Class 2 device (less than 30VAC.) Take
appropriate isolation measures when
mounting an InterOp8500 module where
non-Class 2 devices or wiring are present.
5
InterOp-8500
Power Connector
Power Cable
PWRSUP8500
(side-mounted)
InterOp-8500
Edge Connectors