- ページ 13
コントロールユニット Automated Logic S6104のPDF テクニカル・インストラクションをオンラインで閲覧またはダウンロードできます。Automated Logic S6104 16 ページ。
- 1. Table of Contents
- 2. Using the S6104
- 3. Specifications
- 4. Mounting
- 5. Addressing
- 6. Power Wiring
- 7. Network Communications
- 7. Using the S6104 on an ARC156 Segment
- 7. Using the S6104 on a Legacy Cmnet
- 7. Connecting the S6104 to the Network
- 7. Communicating through the Logistat Port Using Supervision
- 7. Communicating through the Access Port Using Supervision
- 8. Inputs
- 8. Logistat Wiring
Point Identifiers
A point can be identified in WebCTRL by its
point number and point type; in SuperVision,
a point is identified by its channel number. On
both systems, expander number zero
represents I/O points on the S6104.
Point Identifiers in WebCTRL
Enter the point identifiers in Eikon for
WebCTRL before the FB is made or on the FB's
Properties page in WebCTRL. Set the type,
number, and minimum and maximum
present values for each point on the S6104.
Select a physical point type from the point
type field and enter the number of the input or
output. To scale a linear signal type, enter the
appropriate minimum and maximum present
values on the microblock's dialog box.
Channel Numbers in SuperVision
The following tables show the valid channel
numbers for each point on the S6104. The
offset and gain values used depend on the
type of sensor or actuator attached to the I/O
point. You can select the channel number,
offset, and gain using SuperVision's Point
Help feature or Configure Points utility.
Alternatively, you can preconfigure the points
by manually entering the channel number,
offset, and gain in Eikon using the values
shown in the following tables.
Revised 7/30/02 • S6104
Figure 16. Sample GFB for the S6104
Table 6. Analog Output Channel Numbers
Point
AO 1
AO 2
AO 3
AO 4
Table 7. Digital Output Channel Numbers
Point
DO 1
DO 2
DO 3
DO 4
DO 5
DO 6
Table 8. Universal Input Channel Numbers
Point
UI 1
13
Channel
Signal Type
Number
Range
Analog
41
0 to 10VDC
Analog
42
0 to 10VDC
Analog
43
0 to 10VDC
Analog
44
0 to 10VDC
Channel
Signal Type
Number
Digital
11
HOA Status
81
Digital
12
HOA Status
82
Digital
13
HOA Status
83
Digital
14
HOA Status
84
Digital
15
HOA Status
85
Digital
16
HOA Status
86
Channel
Signal Type
Number
†Range
-17° to 213° F
Thermistor
31
-27° to 100.6° C
0 to 20mA
mA or Volts
31
0 to 5V
Digital
21
© 2002 Automated Logic Corporation
Offset
Gain
0.00
0.0625
0.00
0.0625
0.00
0.0625
0.00
0.0625
Offset
Gain
0.00
15.88
0.00
15.69
§
§