Field Installation Manual
Model
Phase Configuration
Maximum Line Voltage
Maximum Power
Steps
Monitoring
Accuracy
Frequency
Protection
Equipment Protection
Circuit breaker Required
Low Losses
Human Protection
Operating temperature range
Dimensions(L X H X D)
Operating Life
Dielectric Strength
Wire Gauge & Rating
Unit Weight
______________________________________________________________________________________
ES-15
Electrical Data Sheet
ES-15
Three Phase 120/208V AC WYE/Delta
208V AC
15 kVar
5
PF, kVA, kVar, Volt, Current, KW, %THD-V
Internal Temperature & Capacitor Status
0.333 kVar each Phase, 1 Kvar three Phase
60Hz
Capacitor Inbuilt Protection P2, capacitor short circuit 10,000A
Capacitor over current protection.
Internal design has adequate clearance and creepage distance
against line transients. MOVs not required.
60 Amp 3 pole
1.5 Watt each step
All High voltage shielded from contact.
o
40
C Ambient
20" X 20" X 8.5" ( 500 x 500 x 210 mm) Metal Enclosure Type 1
Switching tested up to 25,000 times, 6,000 as per UL
Tested up to 3.5 kV, 1.42 kV for 1 min. as per UL
6 AWG Str for Power, 18-22 AWG Str for CT, 10 AWG Str for Bonding
28 kg (62 Pounds)
9