- ページ 3

セキュリティシステム ADEMCO VISTA-15P SeriesのPDF プログラミング・マニュアルをオンラインで閲覧またはダウンロードできます。ADEMCO VISTA-15P Series 17 ページ。
ADEMCO VISTA-15P Series にも: クイック・インストール・マニュアル (2 ページ)

ADEMCO VISTA-15P Series プログラミング・マニュアル
Programmable values apply to all controls, except field *189, which applies to the VISTA-20PS only.
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
Entries shown in dashed boxes indicate partition entries for VISTA-20P only (not applicable for VISTA-15P).
Field
Function
SYSTEM SETUP ( ✱ 20– ✱ 29)
✱ 20 INSTALLER CODE
✱ 21
QUICK ARM ENABLE
✱ 22
RF JAM OPTION
✱ 23
QUICK (FORCED) BYPASS
✱ 24 RF HOUSE ID CODE
✱ 26
CHIME BY ZONE
✱ 27
POWERLINE CARRIER DEVICE (X–10)
HOUSE CODE
✱ 28
ACCESS CODE FOR
PHONE MODULE
✱ 29 LONG RANGE RADIO OUTPUT
ZONE SOUNDS AND TIMING ( ✱ 31 – ✱ 39)
✱ 31
SINGLE ALARM SOUNDING per ZONE
✱ 32
FIRE ALARM SOUNDER TIMEOUT
✱ 33
ALARM SOUNDER (BELL) TIMEOUT
✱ 34
EXIT DELAY
✱ 35
ENTRY DELAY #1 (zone type 01)
✱ 36
ENTRY DELAY #2 (zone type 02)
AUDIBLE EXIT WARNING
∗37
✱ 38
CONFIRMATION OF ARMING DING
✱ 39
POWER UP IN PREVIOUS STATE
DIALER PROGRAMMING ( ✱ 40 – ✱ 42)
Do not fill unused spaces. Enter 0–9; #+11 for ' ✱ '; #+12 for '#'; #+13 for a 2-second pause. If fewer than the maximum digits entered, exit the
field by pressing [✶]. The next data field number is displayed.
✱ 40 PABX ACCESS CODE
✱ 41 PRIMARY PHONE No.
✱ 42 SECOND PHONE No.
www.PDF-Zoo.com
352*5$00,1*)250
Data Entries
|
|
|
Part. 1 Part.2
[0]
Part. 1 Part. 2
|
Part. 1 Part. 2 Common
[0]
[0]
|
[00]
(Partition 1 only)
[0]
[0]
[0]
[1]
|
|
Part. 1 Part. 2
|
Part. 1 Part. 2
Common zones use same
delay as partition 1
|
Part. 1 Part. 2
[1]
Part. 1 Part. 2
[1]
|
|
|
used, enter "∗ (#+11) 70" plus "# + 13" (pause).
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter up to 20 digits. To clear entries, press ✱ 41 ✱ or ✱ 42 ✱ respectively .
Programmable Values
4 digits, 0–9
[4112]
0 = no; 1 = yes
[0,0]
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
0 = no quick bypass UL: must be "0"
[0,0]
1 = allow quick bypass (code + [6] + [#] )
00 = disable all wireless keypad usage
|
|
01–31 = using 5827, 5827BD or 5804BD keypad
[00,00,00]
0 = no; 1 = yes (select zones to chime on zone list 3,
using *81 Menu mode)
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G,
7 = H, 8 = I, 9 = J, #10 = K, #11 = L, #12 = M, #13 = N,
#14 = O, #15 = P UL: not for fire or UL installations
00 = disable; 1st digit: enter 1–9; 2nd digit: enter # + 11
for " ✱ ", or # + 12 for "#".
UL: must be "00" for UL Commercial Burg. installations
0 = disable; 1 = enable
0 = no UL: must be "0"; 1 = yes
0 = sounder stops at timeout;
1 = no sounder timeout UL: must be "1" for fire install.
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min;
UL: For residential fire alarm installation, must be set for a
minimum of 4 min (option 1); for UL Commercial Burglary
installations, must be minimum 16 min (option 4)
00 - 96 = 0 - 96 secs; 97 = 120 secs
[60,60]
SIA Installations: minimum exit delay is 45 seconds
UL: see inst. instr. for requirements.
Common zones use same delay as partition 1.
00 - 96 = 0 - 96 seconds
|
[30,30]
97 = 120 seconds
98 = 180 seconds
99 = 240 seconds
For UL Residential Burglary Alarm installations, must be set
.
for a maximum of 30 seconds; entry delay plus dial delay
should not exceed 1 min. For UL Commercial Burglar Alarm,
total entry delay may not exceed 45 seconds.
See *35 Entry Delay 1 above for entries.
|
[30,30]
0 = no; 1 = yes
SIA Installations: must be enabled (enter 1)
0 = no; 1 = yes (wired keypads and RF)
[0,0]
2 = yes, RF only
UL: must be "1" for UL Commercial Burglar Alarm inst.
0 = no; 1 = yes UL: must be "1"
Enter up to 6 digits. To clear entries, press ✱40✱. If call waiting
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
– 3 –
SIA Installations:
minimum entry delay is
30 seconds