- ページ 16
スイッチ DynaGen AST2225のPDF インストールとユーザーマニュアルをオンラインで閲覧またはダウンロードできます。DynaGen AST2225 19 ページ。 Automatic transfer switch
16
6: FIELD SET-UP
6:1 Locking Mechanism
The AST3225 enclosure can be equipped with an optional locking mechanism
(parts required: locking mechanism and locking mechanism gasket), which
allows the Transfer Switch to be securely locked, and eliminate any form of
tampering with the switch. The locking mechanism can mount on either one of
the quarter turn door latches. The mounting procedure is as follows:
1). Open the door of the enclosure.
2). On the back of the enclosure door, remove the Philips head screw, which
secures the quarter turn latch.
3). Remove the quarter turn latch.
4). From the front of the enclosure, remove the quarter turn insert, rubber
gasket, and flat washer.
5). Remove the lock nut located on the back of the enclosure door.
6). On the back of the enclosure door, gently tap the quarter turn latch housing
until it is free from the door. NOTE: carefully observe how the quarter turn
latch housing is inserted in the door, as it has to be put back in the door in
the exact same manner.
7). Remove the quarter turn latch housing and the quarter turn latch housing
rubber gasket.
8). Place the locking mechanism gasket over the hole in the enclosure door,
and the locking mechanism over the gasket (the hasp on the locking
mechanism would go closest to the edge of the enclosure).
9). Repeat steps 2 through 7 in their reverse order.
Automatic
Manual for AST2225 Series
Transfer Switch