- ページ 5
スイッチ DynaGen AST2225のPDF インストールとユーザーマニュアルをオンラインで閲覧またはダウンロードできます。DynaGen AST2225 19 ページ。 Automatic transfer switch
5
The transfer motor drives a crank that in turn operates an aluminum lever arm, by sliding
a nylon slider between the top and bottom parts of the arm assembly. The lever, in turn,
operates the two switch handles by means of a unique spring and roller arrangement. The
travel position of the aluminum lever is detected by two micro switches, which in turn
disconnect power to the transfer motor, when appropriate.
1:2 Relay Board Module:
The relay board provides means for automatic transfer of a utility source of power to an
emergency source of power, upon loss of the utility, and switches back again, upon
restoration of the utility. The relay board has no built in delays for transfer. Any required
delays must come from an external source (ie. engine controller, timer module).
1:2:1 Sensing:
Voltage sensing is provided by means of an adjustable 3-phase monitor. The 3-phase
monitor continuously monitors 3-phase power lines for abnormal conditions. The
adjustable voltage monitor is a single set-point voltage monitor. Input voltages 10%
below the set-point range will cause the output contacts to de-energize (unit is adjustable
from (190-240 VAC). The adjustable drop out relay recommended for use with the
AST3225-3 Automatic Transfer Switch is the Symcom 201-A
ADJUSTMENT PROCEDURE
Plug in the adjustable voltage monitor. The monitor goes through its restart delay, and the
LED on the monitor flashes red and green. After 4 seconds, the green light comes on
solid. Measure the line to line voltage. Rotate the line voltage adjustment to the nominal
line voltage feeding the transfer switch. The adjustable voltage monitor is configured to
trip when the monitor sees a voltage drop to 90% of the set point voltage.
1:2:2 System Operation:
The relay board module has provisions for 12 and 24 VDC operation. The relay board
comes factory set for 12 VDC applications. Changing from 12 to 24 VDC will require
cutting the 2 jumper wires located next to the 5-position header.
2: INSTALLATION INFORMATION
2:1 General
The basic AST2225-3 transfer switch includes all control wiring connections. The
electrical switchgear should be installed by a certified electrician, and all wiring to/from
the unit should agree with all applicable electrical codes, standards, and practices.
Automatic
Manual for AST2225 Series
Transfer Switch