- ページ 4
コントロールパネル DynaGen TR100のPDF ユーザーマニュアルをオンラインで閲覧またはダウンロードできます。DynaGen TR100 12 ページ。 Digital generator controllers
Introduction
Introduction
1
The TR100-E is a J1939 remote panel for use w ith the TE350 and TE410. In a J1939 netw ork there can be one local engine
controller (TE350 or TE410) paired w ith an unlimited number of remotes (recommend limiting to five remotes).
The remote mimics w hat is displayed on the controller (see
1.1
Limitations
The remote panel cannot communicate w ith more than one local controller and there can only be one local controller on a
single J1939 netw ork.
There are restrictions the remote panel has compared to w hat can be done locally on the controller:
1. The countdow n timers (e.g. delay to start, preheat, cranking, crank rest, w arm-up, ...) are not displayed on the remote.
2. The log cannot be accessed from the remote panel.
3. The aftertreatment (e.g. DPF) menu is not displayed on the remote panel. A DPF/DEF cannot be initiated from the remote
panel.
4. No I/O on the remote panel is supported such as sw itched inputs, sw itched outputs, analog inputs, or modbus (RS485)
communications.
5. The date and time on the remote must be programmed manually. It is not updated over J1939. All custom text (if
applicable) must be programmed to the remote using the RapidCore Configuration softw are.
TOUGH Series Manual
limitations
below ).
© 2019 DynaGen Technologies Inc
3