1. DO NOT use wire smaller than 18 AWG.
2. DO NOT short Run output to ground, as this will cause 20A fuse to blow, and may cause
damage to on board relay contacts.
3. Replace on board 20A fuse with similar type and rating (Replacement fuse to be Blade type
MINI FUSE rated 20 Amps maximum). Never bypass fuse with jumper, as this will not
protect unit in the event of a short circuit or overload condition.
4. DO NOT exceed the maximum rated current and voltage on the BCM output. Do not exceed
10 amps for Run output.
5. Do not reverse power supply connections to the BCM unit as this will result in permanent
damage to unit.
6. Installation of a diode is not required across Run output. An internal fast switching diode is
provided to protect the BCM output from inductive kick-back. However, diodes should be
placed across external slave relay contacts when used to actuate any inductive loads, such as
solenoids, to protect the contacts from damage caused by arcing. In addition to prolonging
the useful life of the relays, placing such diodes will enormously reduce generated electrical
noise.
7.
DO NOT short potentiometer jumpers to ground, as this may result in damage to BCM unit.
These jumpers are located adjacent to the potentiometers on rear of unit, they provide a
method for simple and easy calibration of LOW, HIGH and RUN TIME set points.
8.
There is a potentiometer, which is just below the potting, adjacent to the Run relay. DO NOT
attempt to adjust this pot. This pot has been calibrated at the factory and does not require
field adjustment. Adjusting this pot will greatly affect the sensing accuracy of the BCM unit.
9.
Replace On board relay with similar type and rating. Some replacement types are as follows:
• Bosch
• American Zettler
• Aromat
Operating & Installation Manual for Battery Charge Monitor (BCM)
WIRING GUIDELINES
Part # 0 332 207 307
Part # AZ977-1A-12D
Part # CM1–R –12V
6